Worked example
Example: 35 °C, 40 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Dry-bulb temperature | 35.000 °C |
| Relative humidity | 40.000 % |
| Barometric pressure | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Wet-bulb temperature | 23.934 °C |
| Wet-bulb depression | 11.066 K |
| Dew point | 19.384 °C |
| Humidity ratio | 14.133 g/kg |
| Enthalpy (per kg dry air) | 71.478 kJ/kg |
Open this example in the calculator and change any input.
Formula
\(W = \frac{(2501 - 2.326t_{wb})W_s^* - 1.006(t - t_{wb})}{2501 + 1.86t - 4.186t_{wb}}, \quad W = 0.622\frac{\varphi p_s}{p - \varphi p_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(t\) | Dry-bulb temperature | K |
| \(\varphi\) | Relative humidity | - |
| \(p\) | Barometric pressure | Pa |
| \(t_{wb}\) | Wet-bulb temperature | K |
| \(t - t_{wb}\) | Wet-bulb depression | K |
| \(t_{dp}\) | Dew point | K |
| \(W\) | Humidity ratio | kg/kg |
| \(h\) | Enthalpy (per kg dry air) | J/kg |
Method and standards
ASHRAE eq. (33), solved for t_wb.
Where it is used
- Cooling tower and evaporative cooler design.
- Heat stress and comfort checks.
Common mistakes
- Confusing wet bulb with dew point.
- Ignoring altitude (barometric pressure).
Assumptions and limits
- 0–100 °C; wet bulb above 0 °C.
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 1
- eq. (33) for the thermodynamic wet bulb; IAPWS-IF97 saturation pressure
Questions and answers
Why does wet bulb matter?
It limits evaporative cooling: cooling towers and evaporative coolers cannot cool water or air below it.
Is wet bulb the same as dew point?
No: dew point is lower (unless the air is saturated); wet bulb lies between dew point and dry bulb.
What do the defaults represent?
Hot, moderately dry summer air at sea-level pressure.