Worked example
Example: 35 °C, 50 % RH, sea level. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Dry-bulb temperature | 35.000 °C |
| Second property | Relative humidity |
| Relative humidity | 50.000 % |
| Wet-bulb temperature (ice bulb below 0 °C) | 26.000 °C |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Humidity ratio | 17.768 g/kg |
| Relative humidity | 50.000 % |
| Wet-bulb temperature (ice bulb below 0 °C) | 26.141 °C |
| Dew-point temperature (frost point below 0 °C) | 23.020 °C |
| Enthalpy per kg of dry air | 80.804 kJ/kg |
| Specific volume per kg of dry air | 0.89789 m³/kg |
| Density of the moist air | 1.1335 kg/m³ |
| Partial pressure of water vapour | 2.8143 kPa |
Open this example in the calculator and change any input.
Formula
\(p_v = \varphi\,p_{sat}(T) \qquad W = \frac{M_w}{M_{da}}\,\frac{p_v}{p - p_v}\)
\(h = 1006\,t + W\,(2\,501\,000 + 1860\,t) \qquad v = \frac{R\,T}{M_{da}\,p}\left(1 + \frac{W M_{da}}{M_w}\right) \qquad \rho = \frac{1 + W}{v}\)
\(W = \frac{(2\,501\,000 - 2326\,t_{wb})\,W_{s,wb} - 1006\,(t - t_{wb})}{2\,501\,000 + 1860\,t - 4186\,t_{wb}}\)
Below 0 °C the ice bulb (ASHRAE ch. 1 eq. 35), with \(W_{s,ib}\) over ice, and the frost point \(p_{subl}(T_{fp}) = p_v\) (IAPWS R14-08):
\(W = \frac{(2\,830\,000 - 240\,t_{ib})\,W_{s,ib} - 1006\,(t - t_{ib})}{2\,830\,000 + 1860\,t - 2100\,t_{ib}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T\) | dry-bulb temperature (t in °C) | K |
| \(\text{given}\) | second property entered: RH or wet bulb | – |
| \(\varphi\) | relative humidity | – |
| \(T_{wb}\) | wet-bulb temperature (t_wb in °C) | K |
| \(p\) | barometric pressure | Pa |
| \(W\) | humidity ratio | kg/kg dry air |
| \(T_{dp}\) | dew-point temperature | K |
| \(h\) | enthalpy per kg dry air | J/kg |
| \(v\) | volume per kg dry air | m³/kg |
| \(\rho\) | density of the moist air | kg/m³ |
| \(p_v\) | vapour pressure | Pa |
| \(p_{sat}\) | saturation pressure (IF97) | Pa |
| \(M_w, M_{da}\) | molar masses of water and dry air | kg/kmol |
| \(W_{s,wb}\) | saturation humidity ratio at the wet bulb | kg/kg |
Method and standards
Ideal-gas mixture relations of ASHRAE Handbook—Fundamentals ch. 1: humidity ratio from vapour pressure, enthalpy with 1006, 2 501 000 and 1860 J/kg constants, wet bulb from eq. (33) solved by bisection. Saturation pressure and dew point from IAPWS-IF97.
Where it is used
- Air-handling unit and fresh-air design.
- Control room and switchgear room conditioning.
- Dryer and cooling tower inlet air.
Common mistakes
- Using a sling psychrometer wet bulb in still air (it reads high).
- Mixing kg of moist air with kg of dry air in balances.
- Ignoring altitude at hill sites.
Assumptions and limits
- Dry bulb 0–100 °C. Wet bulb and dew point over liquid water at or above 0 °C; below it the ice bulb and the frost point over ice, down to −60 °C.
- Ideal gas; no enhancement factor (under 0.5 % near 1 atm).
References
- ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
- IAPWS-IF97 saturation pressure
Questions and answers
What are the properties of air at 35 °C and 50 % RH?
At sea level: humidity ratio 17.8 g/kg, wet bulb 26.1 °C, dew point 23.0 °C, enthalpy 80.8 kJ/kg dry air and specific volume 0.898 m³/kg.
Why is enthalpy per kg of dry air?
Dry air passes through a coil or a room unchanged while the water content varies, so balances are written on the dry air.
Does altitude matter?
Yes. At lower barometric pressure the same RH holds more water per kg of dry air; enter the site pressure.