FireCADCalc

Psychrometric Calculator (Moist Air Properties)

Humidity ratio, relative humidity, wet bulb, dew point, enthalpy, specific volume and density of moist air from dry bulb with relative humidity or wet bulb.

IAPWS-IF97 (water and steam)Air conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: 35 °C, 50 % RH, sea levelDry bulb 32 °C, wet bulb 24 °CPlant at 900 m: 28 °C, 70 % RH, 90.6 kPaDry winter air: 10 °C, 20 % RH (frost point)Cold dry air: 4 °C, 20 % RH (ice bulb)

Relative humidity

Wet-bulb temperature

Results

The dew point is below 0 °C: the frost point over ice (IAPWS R14-08) is shown.

Humidity ratio1.5114g/kg
Relative humidity20.000%
Wet-bulb temperature (ice bulb below 0 °C)2.5279°C
Dew-point temperature (frost point below 0 °C)-10.633°C
Enthalpy per kg of dry air13.868kJ/kg
Specific volume per kg of dry air0.80408m³/kg
Density of the moist air1.2455kg/m³
Partial pressure of water vapour0.24564kPa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 35 °C, 50 % RH, sea level. The inputs, in the units selected above:

InputValue
Dry-bulb temperature35.000 °C
Second propertyRelative humidity
Relative humidity50.000 %
Wet-bulb temperature (ice bulb below 0 °C)26.000 °C
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Humidity ratio17.768 g/kg
Relative humidity50.000 %
Wet-bulb temperature (ice bulb below 0 °C)26.141 °C
Dew-point temperature (frost point below 0 °C)23.020 °C
Enthalpy per kg of dry air80.804 kJ/kg
Specific volume per kg of dry air0.89789 m³/kg
Density of the moist air1.1335 kg/m³
Partial pressure of water vapour2.8143 kPa

Open this example in the calculator and change any input.

Formula

\(p_v = \varphi\,p_{sat}(T) \qquad W = \frac{M_w}{M_{da}}\,\frac{p_v}{p - p_v}\)

\(h = 1006\,t + W\,(2\,501\,000 + 1860\,t) \qquad v = \frac{R\,T}{M_{da}\,p}\left(1 + \frac{W M_{da}}{M_w}\right) \qquad \rho = \frac{1 + W}{v}\)

\(W = \frac{(2\,501\,000 - 2326\,t_{wb})\,W_{s,wb} - 1006\,(t - t_{wb})}{2\,501\,000 + 1860\,t - 4186\,t_{wb}}\)

Below 0 °C the ice bulb (ASHRAE ch. 1 eq. 35), with \(W_{s,ib}\) over ice, and the frost point \(p_{subl}(T_{fp}) = p_v\) (IAPWS R14-08):

\(W = \frac{(2\,830\,000 - 240\,t_{ib})\,W_{s,ib} - 1006\,(t - t_{ib})}{2\,830\,000 + 1860\,t - 2100\,t_{ib}}\)

Variables

Symbol Meaning SI unit
\(T\) dry-bulb temperature (t in °C) K
\(\text{given}\) second property entered: RH or wet bulb –
\(\varphi\) relative humidity –
\(T_{wb}\) wet-bulb temperature (t_wb in °C) K
\(p\) barometric pressure Pa
\(W\) humidity ratio kg/kg dry air
\(T_{dp}\) dew-point temperature K
\(h\) enthalpy per kg dry air J/kg
\(v\) volume per kg dry air m³/kg
\(\rho\) density of the moist air kg/m³
\(p_v\) vapour pressure Pa
\(p_{sat}\) saturation pressure (IF97) Pa
\(M_w, M_{da}\) molar masses of water and dry air kg/kmol
\(W_{s,wb}\) saturation humidity ratio at the wet bulb kg/kg

Method and standards

Ideal-gas mixture relations of ASHRAE Handbook—Fundamentals ch. 1: humidity ratio from vapour pressure, enthalpy with 1006, 2 501 000 and 1860 J/kg constants, wet bulb from eq. (33) solved by bisection. Saturation pressure and dew point from IAPWS-IF97.

Where it is used

  • Air-handling unit and fresh-air design.
  • Control room and switchgear room conditioning.
  • Dryer and cooling tower inlet air.

Common mistakes

  • Using a sling psychrometer wet bulb in still air (it reads high).
  • Mixing kg of moist air with kg of dry air in balances.
  • Ignoring altitude at hill sites.

Assumptions and limits

  • Dry bulb 0–100 °C. Wet bulb and dew point over liquid water at or above 0 °C; below it the ice bulb and the frost point over ice, down to −60 °C.
  • Ideal gas; no enhancement factor (under 0.5 % near 1 atm).

References

  • ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
  • IAPWS-IF97 saturation pressure

Questions and answers

What are the properties of air at 35 °C and 50 % RH?

At sea level: humidity ratio 17.8 g/kg, wet bulb 26.1 °C, dew point 23.0 °C, enthalpy 80.8 kJ/kg dry air and specific volume 0.898 m³/kg.

Why is enthalpy per kg of dry air?

Dry air passes through a coil or a room unchanged while the water content varies, so balances are written on the dry air.

Does altitude matter?

Yes. At lower barometric pressure the same RH holds more water per kg of dry air; enter the site pressure.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.