Worked example
Example: Winter air 10 000 m³/h at 20 °C 20 % to 21 °C 45 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow at the entering condition | 10,000 m³/h |
| Atmospheric pressure | 101.33 kPa |
| Entering air temperature | 20.000 °C |
| Entering relative humidity | 20.000 % |
| Supply air temperature after the humidifier | 21.000 °C |
| Target relative humidity | 45.000 % |
| Feed water temperature | 15.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Entering humidity ratio | 2.8850 g/kg |
| Target humidity ratio | 6.9492 g/kg |
| Dry air flow | 11,986 kg/h |
| Steam needed | 48.714 kg/h |
| Power of an electric steam humidifier | 35.352 kW |
Open this example in the calculator and change any input.
Formula
\(W = 0.622\text{-type ratio: } \frac{M_w}{M_a} \frac{\phi\, p_{sat}(T)}{p - \phi\, p_{sat}(T)}\)
\(\dot m_a = Q / v(T_1, W_1), \quad \dot m_s = \dot m_a (W_2 - W_1)\)
\(P = \dot m_s [h_g(1\ \text{atm}) - h_f(T_w)]\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | air flow at the entering condition | m³/s |
| \(p\) | atmospheric pressure | Pa |
| \(T_1\) | entering temperature | K |
| \(\phi_1\) | entering relative humidity | - |
| \(T_2\) | supply temperature | K |
| \(\phi_2\) | target relative humidity | - |
| \(T_w\) | feed water temperature | K |
| \(\phi\) | relative humidity | - |
| \(p_{sat}\) | saturation pressure (IF97) | Pa |
| \(M_w, M_a\) | molar masses of water and dry air | kg/kmol |
| \(v\) | humid volume per kg dry air | m³/kg |
| \(W\) | humidity ratio | kg/kg |
| \(W_1\) | entering humidity ratio | kg/kg |
| \(W_2\) | target humidity ratio | kg/kg |
| \(\dot m_a\) | dry air flow | kg/s |
| \(\dot m_s\) | steam needed | kg/s |
| \(h_g\) | saturated steam enthalpy | J/kg |
| \(h_f\) | feed water enthalpy | J/kg |
| \(P\) | humidifier power | W |
Method and standards
Humidity ratios at the two conditions follow from relative humidity and IF97 saturation pressure; the steam needed is the dry air flow times the rise in humidity ratio. Humidifier power heats feed water to saturated steam at atmospheric pressure.
Where it is used
- Sizing humidifiers for textile mills, clean rooms and offices.
- Estimating humidification energy.
- Checking existing humidifier capacity.
Common mistakes
- Using the room air flow instead of the outdoor-air portion that is dry.
- Forgetting the air is heated before humidifying.
- Using volume flow at a different temperature.
Assumptions and limits
- Steam humidification; no condensation in the duct; no losses.
- Air temperatures from 0 °C (the saturation equation used is over water).
References
- ASHRAE psychrometrics
- IAPWS-IF97 (saturation and steam enthalpy)
Questions and answers
How much steam humidifies 10 000 m³/h from 20 % to 45 % RH?
About 49 kg/h when warming from 20 °C to 21 °C, needing about 35 kW in an electric steam humidifier.
Why does winter air need humidifying?
Cold outdoor air holds little water; heated to room temperature, its relative humidity falls very low.
Does steam heat the air?
Very little: steam injection is nearly isothermal, so the supply temperature stays almost the same.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.