Steam Humidifier Load and Power

Steam needed to humidify an air stream from its entering condition to a target relative humidity, and the power of an electric steam humidifier for it.

IAPWS-IF97 (water and steam)Air conditioning and chillers

Inputs

Examples: Winter air 10 000 m³/h at 20 °C 20 % to 21 °C 45 %Textile mill 50 000 m³/h, 28 °C 40 % to 28 °C 65 %Clean room 3 000 m³/h at 18 °C 30 % to 22 °C 50 %, 95 kPa

Results

Steam injection adds almost no sensible heat; the humidifier power is for raising feed water to steam at atmospheric pressure, with no losses.

Entering humidity ratio9.4284g/kg
Target humidity ratio15.468g/kg
Dry air flow57,733kg/h
Steam needed348.67kg/h
Power of an electric steam humidifier248.98kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Winter air 10 000 m³/h at 20 °C 20 % to 21 °C 45 %. The inputs, in the units selected above:

InputValue
Air flow at the entering condition10,000 m³/h
Atmospheric pressure101.33 kPa
Entering air temperature20.000 °C
Entering relative humidity20.000 %
Supply air temperature after the humidifier21.000 °C
Target relative humidity45.000 %
Feed water temperature15.000 °C

Applying the formula below gives:

ResultValue
Entering humidity ratio2.8850 g/kg
Target humidity ratio6.9492 g/kg
Dry air flow11,986 kg/h
Steam needed48.714 kg/h
Power of an electric steam humidifier35.352 kW

Open this example in the calculator and change any input.

Formula

\(W = 0.622\text{-type ratio: } \frac{M_w}{M_a} \frac{\phi\, p_{sat}(T)}{p - \phi\, p_{sat}(T)}\)

\(\dot m_a = Q / v(T_1, W_1), \quad \dot m_s = \dot m_a (W_2 - W_1)\)

\(P = \dot m_s [h_g(1\ \text{atm}) - h_f(T_w)]\)

Variables

Symbol Meaning SI unit
\(Q\) air flow at the entering condition m³/s
\(p\) atmospheric pressure Pa
\(T_1\) entering temperature K
\(\phi_1\) entering relative humidity -
\(T_2\) supply temperature K
\(\phi_2\) target relative humidity -
\(T_w\) feed water temperature K
\(\phi\) relative humidity -
\(p_{sat}\) saturation pressure (IF97) Pa
\(M_w, M_a\) molar masses of water and dry air kg/kmol
\(v\) humid volume per kg dry air m³/kg
\(W\) humidity ratio kg/kg
\(W_1\) entering humidity ratio kg/kg
\(W_2\) target humidity ratio kg/kg
\(\dot m_a\) dry air flow kg/s
\(\dot m_s\) steam needed kg/s
\(h_g\) saturated steam enthalpy J/kg
\(h_f\) feed water enthalpy J/kg
\(P\) humidifier power W

Method and standards

Humidity ratios at the two conditions follow from relative humidity and IF97 saturation pressure; the steam needed is the dry air flow times the rise in humidity ratio. Humidifier power heats feed water to saturated steam at atmospheric pressure.

Where it is used

  • Sizing humidifiers for textile mills, clean rooms and offices.
  • Estimating humidification energy.
  • Checking existing humidifier capacity.

Common mistakes

  • Using the room air flow instead of the outdoor-air portion that is dry.
  • Forgetting the air is heated before humidifying.
  • Using volume flow at a different temperature.

Assumptions and limits

  • Steam humidification; no condensation in the duct; no losses.
  • Air temperatures from 0 °C (the saturation equation used is over water).

References

  • ASHRAE psychrometrics
  • IAPWS-IF97 (saturation and steam enthalpy)

Questions and answers

How much steam humidifies 10 000 m³/h from 20 % to 45 % RH?

About 49 kg/h when warming from 20 °C to 21 °C, needing about 35 kW in an electric steam humidifier.

Why does winter air need humidifying?

Cold outdoor air holds little water; heated to room temperature, its relative humidity falls very low.

Does steam heat the air?

Very little: steam injection is nearly isothermal, so the supply temperature stays almost the same.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.