Worked example
Example: 10 000 m³/h, 5 to 28 °C, 80/60 °C water. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow (at the inlet) | 10,000 m³/h |
| Air in | 5.0000 °C |
| Inlet relative humidity | 80.000 % |
| Air out | 28.000 °C |
| Hot water in | 80.000 °C |
| Hot water out | 60.000 °C |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Coil load | 81.651 kW |
| Hot water flow | 3.5107 t/h |
| Leaving relative humidity | 18.453 % |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_{da}\left[h(T_2, W) - h(T_1, W)\right], \quad \dot m_w = \frac{\dot Q}{h_{w1} - h_{w2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow (at the inlet) | m³/s |
| \(T_1\) | Air in | K |
| \(\varphi_1\) | Inlet relative humidity | - |
| \(T_2\) | Air out | K |
| \(T_{w1}\) | Hot water in | K |
| \(T_{w2}\) | Hot water out | K |
| \(p\) | Barometric pressure (absolute) | Pa |
| \(\dot Q\) | Coil load | W |
| \(\dot m_w\) | Hot water flow | kg/s |
| \(\varphi_2\) | Leaving relative humidity | - |
Method and standards
Energy balance.
Where it is used
- AHU and fresh-air unit heating coils.
- Hot water pump sizing.
Common mistakes
- Volume at the outlet.
- Water ΔT too large for the coil.
Assumptions and limits
- Steady state. Hot water up to 179.9 °C (liquid at the 10 bar(a) used for its properties).
References
- Moist-air energy balance (ASHRAE Handbook—Fundamentals ch. 1); water enthalpies from IAPWS-IF97
Questions and answers
10,000 m³/h from 5 to 28 °C with 80/60 °C water?
About 82 kW and 3.5 t/h of hot water.
Frost?
Coils with outdoor air below 0 °C need frost protection.
Steam coil?
Steam flow = load / latent heat at the coil pressure.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.