Evaporative Cooler Outlet Temperature

Air leaving a direct evaporative cooler or air washer from the inlet dry bulb, humidity and saturation efficiency, with outlet humidity and water evaporated.

IAPWS-IF97 (water and steam)Air conditioning and chillers

Inputs

Examples: 40 °C, 25 % RH, 85 % pad, 10 000 m³/hDry summer 44 °C, 15 %, 90 %, 20 000 m³/hHumid 33 °C, 60 %, 80 %, 5000 m³/h

From the cooler maker; depends on pad depth and face velocity.

Results

The process is taken at constant enthalpy (adiabatic saturation); pump heat and make-up water temperature are neglected.

Outlet dry bulb26.066°C
Outlet relative humidity80.557%
Inlet wet bulb23.607°C
Outlet humidity ratio17.157g/kg
Water evaporated62.149kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 40 °C, 25 % RH, 85 % pad, 10 000 m³/h. The inputs, in the units selected above:

InputValue
Inlet dry bulb40.000 °C
Inlet relative humidity25.000 %
Saturation efficiency of the pad or washer85.000 %
Air flow (at the inlet state)10,000 m³/h
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Outlet dry bulb26.066 °C
Outlet relative humidity80.557 %
Inlet wet bulb23.607 °C
Outlet humidity ratio17.157 g/kg
Water evaporated62.149 kg/h

Open this example in the calculator and change any input.

Formula

\(T_2 = T_1 - \varepsilon\,(T_1 - T_{wb}) \qquad h_2 = h_1 \qquad W_2 = \frac{h_1 - 1006\,t_2}{2\,501\,000 + 1860\,t_2} \qquad \dot m_w = \dot m_{da}(W_2 - W_1)\)

Variables

Symbol Meaning SI unit
\(T_1\) inlet dry bulb K
\(\varphi_1\) inlet RH –
\(\varepsilon\) saturation efficiency –
\(\dot V\) air flow at inlet m³/s
\(p\) barometric pressure Pa
\(T_2\) outlet dry bulb (t_2 in °C) K
\(\varphi_2\) outlet RH –
\(T_{wb}\) inlet wet bulb K
\(W_2\) outlet humidity ratio kg/kg
\(\dot m_w\) water evaporated kg/s
\(h_1\) inlet enthalpy J/kg
\(\dot m_{da}\) dry-air flow kg/s

Method and standards

Direct evaporative cooling follows the wet-bulb line at nearly constant enthalpy; the saturation (wet-bulb) efficiency sets how close the outlet comes to the wet bulb. Moist-air relations from ASHRAE ch. 1.

Where it is used

  • Turbine and engine inlet air cooling.
  • Spot cooling in boiler houses and workshops.
  • Pre-cooling condenser air.

Common mistakes

  • Using RH instead of the wet bulb to judge cooling potential.
  • Forgetting the humidity rise inside the space.
  • No bleed-off: scaling of pads.

Assumptions and limits

  • Constant enthalpy; pump heat and make-up water temperature neglected.

References

  • ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
  • IAPWS-IF97 saturation pressure

Questions and answers

How cold will a 40 °C, 25 % RH inlet get with an 85 % pad?

The wet bulb is 23.6 °C, so the air leaves at 26.1 °C and 80.6 % RH; 10 000 m³/h evaporates about 62 kg/h of water.

What limits evaporative cooling?

The inlet wet bulb: air cannot be cooled below it, so it works best in dry weather.

Why add make-up beyond evaporation?

Bleed-off controls salts in the sump; it is extra water, not cooling.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.