Outdoor Air Share for a Target Mixed Air Temperature

Outdoor air share of a mixing box to reach a target mixed air temperature from the return and outdoor temperatures, with the outdoor and return air flows.

Inputs

Examples: 24 °C return, 10 °C outdoor, 13 °C targetHot outdoor: minimum airVery cold outdoor still above target

Results

Sensible mixing by volume, close enough for dampers; the share is held between the minimum and 100 %.

Outdoor air share15.000%
Outdoor air3,000.0m³/h
Return air17,000m³/h
Mixed temperature actually reached25.650°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 24 °C return, 10 °C outdoor, 13 °C target. The inputs, in the units selected above:

InputValue
Return air temperature24.000 °C
Outdoor air temperature10.000 °C
Target mixed air temperature13.000 °C
Total supply air flow20,000 m³/h
Minimum outdoor air share15.000 %

Applying the formula below gives:

ResultValue
Outdoor air share78.571 %
Outdoor air15,714 m³/h
Return air4,285.7 m³/h
Mixed temperature actually reached13.000 °C

Open this example in the calculator and change any input.

Formula

\(x = \min\left[1,\ \max\left(x_{min},\ \frac{T_r - T_m}{T_r - T_o}\right)\right], \quad T_m^{\prime} = T_r + x(T_o - T_r)\)

Variables

Symbol Meaning SI unit
\(T_r\) Return air temperature K
\(T_o\) Outdoor air temperature K
\(T_m\) Target mixed air temperature K
\(\dot V\) Total supply air flow m³/s
\(x_{min}\) Minimum outdoor air share -
\(x\) Outdoor air share -
\(\dot V_o\) Outdoor air m³/s
\(\dot V_r\) Return air m³/s
\(T_m'\) Mixed temperature actually reached K

Method and standards

Mixing balance.

Where it is used

  • AHU economiser control.
  • Commissioning dampers.

Common mistakes

  • Ignoring the minimum fresh air.
  • Stratified mixing boxes.

Assumptions and limits

  • Perfect mixing.

References

  • Sensible mixing balance T_m = T_r + x(T_o − T_r)

Questions and answers

Return 24 °C, outdoor 10 °C, target 13 °C?

About 79 % outdoor air.

Outdoor warmer than return?

The share falls to the minimum: free cooling is not possible.

Frost risk?

Very cold outdoor air with poor mixing can freeze coils; keep a low-limit.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.