Worked example
Example: 24 °C return, 10 °C outdoor, 13 °C target. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Return air temperature | 24.000 °C |
| Outdoor air temperature | 10.000 °C |
| Target mixed air temperature | 13.000 °C |
| Total supply air flow | 20,000 m³/h |
| Minimum outdoor air share | 15.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Outdoor air share | 78.571 % |
| Outdoor air | 15,714 m³/h |
| Return air | 4,285.7 m³/h |
| Mixed temperature actually reached | 13.000 °C |
Open this example in the calculator and change any input.
Formula
\(x = \min\left[1,\ \max\left(x_{min},\ \frac{T_r - T_m}{T_r - T_o}\right)\right], \quad T_m^{\prime} = T_r + x(T_o - T_r)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_r\) | Return air temperature | K |
| \(T_o\) | Outdoor air temperature | K |
| \(T_m\) | Target mixed air temperature | K |
| \(\dot V\) | Total supply air flow | m³/s |
| \(x_{min}\) | Minimum outdoor air share | - |
| \(x\) | Outdoor air share | - |
| \(\dot V_o\) | Outdoor air | m³/s |
| \(\dot V_r\) | Return air | m³/s |
| \(T_m'\) | Mixed temperature actually reached | K |
Method and standards
Mixing balance.
Where it is used
- AHU economiser control.
- Commissioning dampers.
Common mistakes
- Ignoring the minimum fresh air.
- Stratified mixing boxes.
Assumptions and limits
- Perfect mixing.
References
- Sensible mixing balance T_m = T_r + x(T_o − T_r)
Questions and answers
Return 24 °C, outdoor 10 °C, target 13 °C?
About 79 % outdoor air.
Outdoor warmer than return?
The share falls to the minimum: free cooling is not possible.
Frost risk?
Very cold outdoor air with poor mixing can freeze coils; keep a low-limit.