Mixing of Two Air Streams (Psychrometric)

Temperature, humidity and enthalpy of the mixture of two moist-air streams, such as fresh and return air, by mass and energy balance on dry air.

IAPWS-IF97 (water and steam)Air conditioning and chillers

Inputs

Examples: Fresh 2000 m³/h at 35 °C 60 % with return 8000 m³/h at 24 °C 50 %Equal flows 30 °C 40 % and 20 °C 60 %Winter fresh air 5 °C 80 % 1500 m³/h with 22 °C 40 % 6000 m³/h

Results

Mixed air dry bulb24.917°C
Mixed air relative humidity49.098%
Mixed air humidity ratio9.6530g/kg
Mixed air enthalpy per kg of dry air49.656kJ/kg
Total dry-air mass flow8,396.6kg/h
Share of stream 1 in the dry air49.088%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Fresh 2000 m³/h at 35 °C 60 % with return 8000 m³/h at 24 °C 50 %. The inputs, in the units selected above:

InputValue
Stream 1 volume flow (at its own state)2,000.0 m³/h
Stream 1 dry bulb35.000 °C
Stream 1 relative humidity60.000 %
Stream 2 volume flow (at its own state)8,000.0 m³/h
Stream 2 dry bulb24.000 °C
Stream 2 relative humidity50.000 %
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Mixed air dry bulb26.142 °C
Mixed air relative humidity54.802 %
Mixed air humidity ratio11.623 g/kg
Mixed air enthalpy per kg of dry air55.932 kJ/kg
Total dry-air mass flow11,578 kg/h
Share of stream 1 in the dry air19.128 %

Open this example in the calculator and change any input.

Formula

\(\dot m_{da,i} = \frac{\dot V_i}{v_i} \qquad W_m = \frac{\sum \dot m_{da,i} W_i}{\sum \dot m_{da,i}} \qquad h_m = \frac{\sum \dot m_{da,i} h_i}{\sum \dot m_{da,i}}\)

\(t_m = \frac{h_m - 2\,501\,000\,W_m}{1006 + 1860\,W_m}\)

Variables

Symbol Meaning SI unit
\(\dot V_1\) stream 1 volume flow m³/s
\(T_1\) stream 1 dry bulb K
\(\varphi_1\) stream 1 RH –
\(\dot V_2\) stream 2 volume flow m³/s
\(T_2\) stream 2 dry bulb K
\(\varphi_2\) stream 2 RH –
\(p\) barometric pressure Pa
\(T_m\) mixed dry bulb (t_m in °C) K
\(\varphi_m\) mixed RH –
\(W_m\) mixed humidity ratio kg/kg
\(h_m\) mixed enthalpy J/kg
\(\dot m_{da}\) dry-air mass flow kg/s
\(x_1\) stream 1 share of dry air –
\(v_i\) specific volume per kg dry air m³/kg

Method and standards

Adiabatic mixing of moist air on a dry-air basis (ASHRAE Handbook—Fundamentals ch. 1); properties of each stream as in the psychrometric calculator.

Where it is used

  • Fresh and return air in air-handling units.
  • Combustion air mixing.
  • Dryer exhaust recirculation.

Common mistakes

  • Weighting by volume at different temperatures.
  • Averaging RH.
  • Ignoring fog when very cold air meets humid air.

Assumptions and limits

  • Steady flow, no heat exchange with the duct; pressure the same for both streams.

References

  • ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
  • IAPWS-IF97 saturation pressure

Questions and answers

What is the mix of 2000 m³/h at 35 °C 60 % and 8000 m³/h at 24 °C 50 %?

26.1 °C, 54.8 % RH, 11.6 g/kg; stream 1 is 19.1 % of the dry air.

Can I average the temperatures by volume?

Roughly, but the correct weighting is dry-air mass, and enthalpy and moisture mix linearly, not temperature or RH.

Why can the mix be supersaturated?

Mixing very cold and warm humid air can cross the saturation line: fog forms.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.