FireCADCalc

Static Regain Duct Sizing of the Next Section

Diameter of a downstream duct section so the static regain from slowing the air equals that section's friction loss, keeping static pressure equal at each branch.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative 12 m/s trunk to a 2 m3/s sectionHigh velocity 18 m/s, 1 m3/sLow velocity 8 m/s, long run

Accepted: 2 to 40 m/s
Accepted: 36 to 180,000 m³/h
Accepted: 0.5 to 200 m
Accepted: 30 to 100 %
Accepted: 0 to 5 mm
Accepted: 0.6 to 1.4 kg/m³
Accepted: 0.01 to 0.03 mPa·s

Results

Solve R·ρ(v₁² − v₂²)/2 = f(L/D)ρv₂²/2 for D: the velocity drop after each branch recovers enough static pressure to overcome the next section's friction, so every outlet sees the same static pressure. Regain coefficients of about 0.5–0.9 allow for losses in the transition. Round to the next standard size and recheck.

Next section diameter509.69mm
Next section velocity9.8024m/s
Static regain21.561Pa
Friction loss of the next section21.561Pa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 12 m/s trunk to a 2 m3/s section. The inputs, in the units selected above:

InputValue
Velocity in the upstream section12.000 m/s
Flow in the next section7,200.0 m³/h
Equivalent length of the next section12.000 m
Regain coefficient75.000 %
Duct roughness0.090000 mm
Air density1.2000 kg/m³
Air viscosity0.018100 mPa·s

Applying the formula below gives:

ResultValue
Next section diameter509.69 mm
Next section velocity9.8024 m/s
Static regain21.561 Pa
Friction loss of the next section21.561 Pa

Open this example in the calculator and change any input.

Formula

\(R\frac{\rho(v_1^2 - v_2^2)}{2} = f\frac{L}{D_2}\frac{\rho v_2^2}{2}, \quad v_2 = \frac{4Q_2}{\pi D_2^2}\)

Variables

Symbol Meaning SI unit
\(v_1\) Velocity in the upstream section m/s
\(Q_2\) Flow in the next section m³/s
\(L\) Equivalent length of the next section m
\(R\) Regain coefficient -
\(\varepsilon\) Duct roughness m
\(\rho\) Air density kg/m³
\(\mu\) Air viscosity Pa·s
\(D_2\) Next section diameter m
\(v_2\) Next section velocity m/s
\(\Delta p_r\) Static regain Pa
\(\Delta p_f\) Friction loss of the next section Pa

Method and standards

Static regain.

Where it is used

  • Large supply air systems.
  • High-velocity and VAV trunk ducts.

Common mistakes

  • Applying it to return ducts.
  • Forgetting fittings in the equivalent length.

Assumptions and limits

  • Round ducts; incompressible air; Colebrook friction.

References

  • Static regain method

Questions and answers

Why use static regain instead of equal friction?

It keeps static pressure nearly equal at every outlet, so long, high-velocity systems need less balancing.

What is the regain coefficient?

The fraction of the theoretical velocity-pressure drop recovered as static pressure, lower for abrupt transitions.

What do the defaults represent?

An illustrative trunk at 12 m/s feeding a 2 m³/s section 12 m long (equivalent), with R = 0.75 and galvanised duct.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

McQuiston, Parker and Spitler, Heating, Ventilating and Air Conditioning: Analysis and Design, 6th ed. (Wiley, 2005)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.