Worked example
Example: Illustrative 12 m/s trunk to a 2 m3/s section. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Velocity in the upstream section | 12.000 m/s |
| Flow in the next section | 7,200.0 m³/h |
| Equivalent length of the next section | 12.000 m |
| Regain coefficient | 75.000 % |
| Duct roughness | 0.090000 mm |
| Air density | 1.2000 kg/m³ |
| Air viscosity | 0.018100 mPa·s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Next section diameter | 509.69 mm |
| Next section velocity | 9.8024 m/s |
| Static regain | 21.561 Pa |
| Friction loss of the next section | 21.561 Pa |
Open this example in the calculator and change any input.
Formula
\(R\frac{\rho(v_1^2 - v_2^2)}{2} = f\frac{L}{D_2}\frac{\rho v_2^2}{2}, \quad v_2 = \frac{4Q_2}{\pi D_2^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(v_1\) | Velocity in the upstream section | m/s |
| \(Q_2\) | Flow in the next section | m³/s |
| \(L\) | Equivalent length of the next section | m |
| \(R\) | Regain coefficient | - |
| \(\varepsilon\) | Duct roughness | m |
| \(\rho\) | Air density | kg/m³ |
| \(\mu\) | Air viscosity | Pa·s |
| \(D_2\) | Next section diameter | m |
| \(v_2\) | Next section velocity | m/s |
| \(\Delta p_r\) | Static regain | Pa |
| \(\Delta p_f\) | Friction loss of the next section | Pa |
Method and standards
Static regain.
Where it is used
- Large supply air systems.
- High-velocity and VAV trunk ducts.
Common mistakes
- Applying it to return ducts.
- Forgetting fittings in the equivalent length.
Assumptions and limits
- Round ducts; incompressible air; Colebrook friction.
References
- Static regain method
Questions and answers
Why use static regain instead of equal friction?
It keeps static pressure nearly equal at every outlet, so long, high-velocity systems need less balancing.
What is the regain coefficient?
The fraction of the theoretical velocity-pressure drop recovered as static pressure, lower for abrupt transitions.
What do the defaults represent?
An illustrative trunk at 12 m/s feeding a 2 m³/s section 12 m long (equivalent), with R = 0.75 and galvanised duct.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
McQuiston, Parker and Spitler, Heating, Ventilating and Air Conditioning: Analysis and Design, 6th ed. (Wiley, 2005)