Lined Duct Attenuation (Sabine's Formula)

Sound attenuation per metre and over a length of an acoustically lined rectangular or round duct from lining absorption coefficient, perimeter and free area.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative 400 x 300 lined duct, 4 mRound 300 mm, 3 mNarrow splitter passage capped at 40 dB

Accepted: 50 to 3,000 mm
Accepted: 50 to 3,000 mm
Accepted: 1 to 100 %
Accepted: 0.1 to 50 m

Results

Sabine: ΔL′ = 1.05α^1.4·P/S dB per unit length (P/S in the same length unit). Good at mid frequencies for ducts below about 0.6 m; above the frequency where the wavelength is smaller than the duct (beaming) attenuation drops sharply, and flanking and regenerated noise cap the total (here at 40 dB). Use measured insertion loss for silencers.

Perimeter-to-area ratio11.6671/m
Attenuation per metre5.9917
Attenuation over the length23.967

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 400 x 300 lined duct, 4 m. The inputs, in the units selected above:

InputValue
Duct shapeRectangular (lined all round)
Free width (or diameter)400.00 mm
Free height (rectangular)300.00 mm
Lining absorption coefficient at the band60.000 %
Lined length4.0000 m

Applying the formula below gives:

ResultValue
Perimeter-to-area ratio11.667 1/m
Attenuation per metre5.9917
Attenuation over the length23.967

Open this example in the calculator and change any input.

Formula

\(\Delta L' = 1.05\alpha^{1.4}\frac{P}{S}, \quad \Delta L = \Delta L'L\)

Variables

Symbol Meaning SI unit
\(\text{shape}\) Duct shape -
\(w\) Free width (or diameter) m
\(h\) Free height (rectangular) m
\(\alpha\) Lining absorption coefficient at the band -
\(L\) Lined length m
\(P/S\) Perimeter-to-area ratio 1/m
\(\Delta L'\) Attenuation per metre -
\(\Delta L\) Attenuation over the length -

Method and standards

Lined duct.

Where it is used

  • HVAC noise control near fans and plant rooms.
  • First estimate before silencer selection.

Common mistakes

  • Applying it at frequencies where the duct beams.
  • Expecting more than 40–50 dB from lining alone.

Assumptions and limits

  • Mid-frequency bands; no flow regenerated noise; fully lined perimeter.

References

  • Sabine's lined duct formula

Questions and answers

Why are narrow ducts better?

A larger lined perimeter per unit area lets sound interact with the absorber more, so P/S drives attenuation.

Why does high-frequency attenuation fall in large ducts?

Sound beams straight down the duct without touching the lining once the wavelength is small compared with the duct.

What do the defaults represent?

An illustrative 400 × 300 mm lined duct with α = 0.6 in the band, 4 m long.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bies and Hansen, Engineering Noise Control, 4th ed. (Spon, 2009)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.