FireCADCalc

Grille and Diffuser: Face and Free-Area Velocity

Face velocity and free-area (core) velocity of a supply or return grille from air flow, size and free-area ratio, and the number of grilles for a target velocity.

Inputs

Examples: Two 600 × 300 grillesLouvre 1200 × 600

From the grille maker.
Lower for quiet rooms and return grilles near people.

Results

Face velocity3.4722m/s
Free-area (core) velocity6.9444m/s
Grilles needed for the target (rounded up)2.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Two 600 × 300 grilles. The inputs, in the units selected above:

InputValue
Total air flow4,000.0 m³/h
Grille width600.00 mm
Grille height300.00 mm
Free-area ratio70.000 %
Number of grilles2.0000 -
Target face velocity (on the gross W × H, not the core)2.0000 m/s

Applying the formula below gives:

ResultValue
Face velocity3.0864 m/s
Free-area (core) velocity4.4092 m/s
Grilles needed for the target (rounded up)4.0000

Open this example in the calculator and change any input.

Formula

\(v_f = \frac{\dot V}{n W H}, \quad v_c = \frac{v_f}{f}, \quad n_t = \left\lceil\frac{\dot V}{W H v_t}\right\rceil\)

Variables

Symbol Meaning SI unit
\(\dot V\) Total air flow m³/s
\(W\) Grille width m
\(H\) Grille height m
\(f\) Free-area ratio -
\(n\) Number of grilles -
\(v_t\) Target face velocity (on the gross W × H, not the core) m/s
\(v_f\) Face velocity m/s
\(v_c\) Free-area (core) velocity m/s
\(n_t\) Grilles needed for the target (rounded up) -

Method and standards

Continuity.

Where it is used

  • Supply and return grille selection.
  • Louvres for plant rooms.

Common mistakes

  • Gross area for core velocity.
  • One grille's flow as the total.

Assumptions and limits

  • Uniform flow. The target is a face velocity on the gross grille area W × H; the core velocity on the free area is higher by 1/f.

References

  • Continuity v = V̇/A; core velocity on the free area

Questions and answers

4000 m³/h through two 600 × 300 grilles?

About 3.1 m/s face, 4.4 m/s through the free area.

Why keep it low?

Noise and draughts rise quickly with velocity.

Louvres on outside walls?

Keep the free-area velocity low enough to stop rain being drawn in.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.