Local Exhaust Hood Flow for a Capture Velocity (Dalla Valle)

Exhaust flow for a plain or flanged hood to reach a capture velocity at a distance from its face (Dalla Valle), face velocity and duct transport velocity.

Thermal power plantProcess steam and utilitiesChemical and fertiliser

Inputs

Examples: Illustrative flanged hood at 300 mmPlain welding hood at 400 mmGrinding hood, 2.5 m/s at 150 mm

Accepted: 0.1 to 10 m/s
Accepted: 10 to 2,000 mm
Accepted: 0.001 to 5 m²
Accepted: 50 to 2,000 mm

Results

Dalla Valle: Q = V_c(10x² + A) for a plain opening, 25 % less with a flange; valid for x up to about 1.5 times the face diameter. Flow rises with the square of distance, so move hoods close to the source. Capture velocities run from about 0.25–0.5 m/s for quiet release to 2.5–10 m/s for grinding; duct velocities must also keep dust airborne.

Exhaust flow3,042.0m³/h
Face velocity9.3889m/s
Duct transport velocity26.897m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative flanged hood at 300 mm. The inputs, in the units selected above:

InputValue
Capture velocity at the source0.75000 m/s
Distance from hood face to source300.00 mm
Hood face area0.12000 m²
Hood typeFlanged opening
Duct diameter250.00 mm

Applying the formula below gives:

ResultValue
Exhaust flow2,065.5 m³/h
Face velocity4.7812 m/s
Duct transport velocity11.688 m/s

Open this example in the calculator and change any input.

Formula

\(Q = V_c(10x^2 + A)\ \text{(plain)}, \quad Q = 0.75V_c(10x^2 + A)\ \text{(flanged)}\)

Variables

Symbol Meaning SI unit
\(V_c\) Capture velocity at the source m/s
\(x\) Distance from hood face to source m
\(A\) Hood face area m²
\(\text{type}\) Hood type -
\(d\) Duct diameter m
\(Q\) Exhaust flow m³/s
\(V_f\) Face velocity m/s
\(V_d\) Duct transport velocity m/s

Method and standards

Hood flow.

Where it is used

  • Welding, grinding and fume extraction.
  • Laboratory and process local exhaust.

Common mistakes

  • Placing hoods far from the source.
  • Ignoring cross-drafts that exceed the capture velocity.

Assumptions and limits

  • Free-standing opening; x up to about 1.5 face diameters.

References

  • Dalla Valle centreline velocity equation
  • ACGIH
  • Industrial Ventilation: A Manual of Recommended Practice for Design (ACGIH)

Questions and answers

Why does distance matter so much?

Air is drawn from all directions, so the velocity falls roughly with the square of distance from the face.

What does a flange do?

It stops air being drawn from behind the hood, so about 25 % less flow gives the same capture velocity.

What do the defaults represent?

An illustrative flanged 0.12 m² hood capturing at 0.75 m/s at 300 mm, ducted in 250 mm pipe.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Dalla Valle, Exhaust Hoods (Industrial Press, 1952)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.