FireCADCalc

Duct Velocity and Velocity Pressure

Air velocity and velocity pressure in a round or rectangular duct from flow and size, with the air density from temperature and pressure.

Inputs

Examples: Rectangular 600 × 400 at 20 °CRound 500 mm flue gas duct at 150 °C

Results

Air density (dry air)1.2042kg/m³
Velocity9.2593m/s
Velocity pressure ρv²/25.2636mmWC

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Rectangular 600 × 400 at 20 °C. The inputs, in the units selected above:

InputValue
Air flow8,000.0 m³/h
Duct shapeRectangular
Diameter (round)500.00 mm
Width (rectangular)600.00 mm
Height (rectangular)400.00 mm
Air temperature20.000 °C
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Air density (dry air)1.2042 kg/m³
Velocity9.2593 m/s
Velocity pressure ρv²/25.2636 mmWC

Open this example in the calculator and change any input.

Formula

\(v = \frac{\dot V}{A}, \quad p_v = \frac{\rho v^2}{2}, \quad \rho = \frac{p M}{R T}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow m³/s
\(\text{shape}\) Duct shape -
\(D\) Diameter (round) m
\(W\) Width (rectangular) m
\(H\) Height (rectangular) m
\(T\) Air temperature K
\(p\) Barometric pressure (absolute) Pa
\(\rho\) Air density (dry air) kg/m³
\(v\) Velocity m/s
\(p_v\) Velocity pressure ρv²/2 Pa

Method and standards

Bernoulli.

Where it is used

  • Duct design and fitting losses.
  • Pitot traverses.

Common mistakes

  • Standard density at high temperature.
  • Gross instead of inside dimensions.

Assumptions and limits

  • Uniform velocity.
  • Dry air of standard composition: humidity and flue-gas composition change the density (flue gas is often 3–5 % denser than air at the same temperature), so for flue gas use a calculator that takes its density.

References

  • Velocity pressure p_v = ρv²/2 (ASHRAE Handbook—Fundamentals (2017), ch. 21); dry-air density from the ideal gas law

Questions and answers

8000 m³/h in a 600 × 400 duct at 20 °C?

About 9.3 m/s and 52 Pa of velocity pressure.

Why does density matter?

Hot flue gas ducts have far lower velocity pressure for the same speed.

Pitot readings?

Invert: v = √(2p_v/ρ).

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators