Worked example
Example: Rectangular 600 × 400 at 20 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow | 8,000.0 m³/h |
| Duct shape | Rectangular |
| Diameter (round) | 500.00 mm |
| Width (rectangular) | 600.00 mm |
| Height (rectangular) | 400.00 mm |
| Air temperature | 20.000 °C |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air density (dry air) | 1.2042 kg/m³ |
| Velocity | 9.2593 m/s |
| Velocity pressure ρv²/2 | 5.2636 mmWC |
Open this example in the calculator and change any input.
Formula
\(v = \frac{\dot V}{A}, \quad p_v = \frac{\rho v^2}{2}, \quad \rho = \frac{p M}{R T}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow | m³/s |
| \(\text{shape}\) | Duct shape | - |
| \(D\) | Diameter (round) | m |
| \(W\) | Width (rectangular) | m |
| \(H\) | Height (rectangular) | m |
| \(T\) | Air temperature | K |
| \(p\) | Barometric pressure (absolute) | Pa |
| \(\rho\) | Air density (dry air) | kg/m³ |
| \(v\) | Velocity | m/s |
| \(p_v\) | Velocity pressure ρv²/2 | Pa |
Method and standards
Bernoulli.
Where it is used
- Duct design and fitting losses.
- Pitot traverses.
Common mistakes
- Standard density at high temperature.
- Gross instead of inside dimensions.
Assumptions and limits
- Uniform velocity.
- Dry air of standard composition: humidity and flue-gas composition change the density (flue gas is often 3–5 % denser than air at the same temperature), so for flue gas use a calculator that takes its density.
References
- Velocity pressure p_v = ρv²/2 (ASHRAE Handbook—Fundamentals (2017), ch. 21); dry-air density from the ideal gas law
Questions and answers
8000 m³/h in a 600 × 400 duct at 20 °C?
About 9.3 m/s and 52 Pa of velocity pressure.
Why does density matter?
Hot flue gas ducts have far lower velocity pressure for the same speed.
Pitot readings?
Invert: v = √(2p_v/ρ).
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.