Duct Heat Gain or Loss and Air Temperature Change

Heat gained or lost by air in a duct running through a warmer or colder space, and the leaving air temperature, from flow, duct size, length and U-value.

Inputs

Examples: Supply at 13 °C through a 40 °C roof voidWarm air duct losing heat outdoors

About 0.6–1 W/m²K with 25–50 mm insulation, 5–8 bare.

Results

Air temperature leaving41.036°C
Temperature change-3.9645K
Heat gained (negative: lost)-3.9882kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Supply at 13 °C through a 40 °C roof void. The inputs, in the units selected above:

InputValue
Air flow6,000.0 m³/h
Duct width600.00 mm
Duct height400.00 mm
Length through the space30.000 m
Duct U-value (per outer surface area)0.80000 W/(m²·K)
Air temperature entering13.000 °C
Surrounding temperature40.000 °C
Air density1.2000 kg/m³
Air specific heat1.0060 kJ/(kg·K)

Applying the formula below gives:

ResultValue
Air temperature leaving13.637 °C
Temperature change0.63651 K
Heat gained (negative: lost)1.2807 kW

Open this example in the calculator and change any input.

Formula

\(T_2 = T_a + (T_1 - T_a)\exp\left(-\frac{U\,2(W + H)L}{\rho \dot V c_p}\right), \quad \dot Q = \rho \dot V c_p (T_2 - T_1)\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow m³/s
\(W\) Duct width m
\(H\) Duct height m
\(L\) Length through the space m
\(U\) Duct U-value (per outer surface area) W/(m²·K)
\(T_1\) Air temperature entering K
\(T_a\) Surrounding temperature K
\(\rho\) Air density kg/m³
\(c_p\) Air specific heat J/(kg·K)
\(T_2\) Air temperature leaving K
\(\Delta T\) Temperature change K
\(\dot Q\) Heat gained (negative: lost) W

Method and standards

Energy balance along the duct.

Where it is used

  • Long supply ducts through hot roof spaces.
  • Insulation decisions.

Common mistakes

  • Linear approximation on long ducts.
  • Inner instead of outer surface area.

Assumptions and limits

  • Constant U and surroundings.
  • The perimeter 2(W + H) uses the dimensions entered: with U per outer surface area, enter the outside (insulated) dimensions; thick insulation makes the outer perimeter noticeably larger than the sheet size.

References

  • Incropera
  • DeWitt
  • Bergman and Lavine
  • Fundamentals of Heat and Mass Transfer
  • ch. 8 (mean temperature in a duct with a uniform external temperature, T₂ = T_a + (T₁ − T_a) exp(−UPL/ṁc_p))

Questions and answers

6000 m³/h at 13 °C through 30 m of a 40 °C roof void?

The air warms about 0.6 K: some 1.3 kW of gain.

Why exponential?

The driving difference shrinks as the air warms.

Bare duct?

With U 6 W/m²K the rise is several times larger.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.