FireCADCalc

Duct Fitting Losses from Loss Coefficients

Pressure loss of up to six kinds of duct fittings from their loss coefficients (C), counts and the velocity pressure, with the total.

Inputs

Examples: Typical branch at 8 m/sSix fittings at 12 m/s

Fitting 1

From a fitting loss table (ASHRAE, SMACNA or the maker).

Fitting 2

From a fitting loss table (ASHRAE, SMACNA or the maker).

Fitting 3

From a fitting loss table (ASHRAE, SMACNA or the maker).

Fitting 4

From a fitting loss table (ASHRAE, SMACNA or the maker).

Fitting 5

From a fitting loss table (ASHRAE, SMACNA or the maker).

Fitting 6

From a fitting loss table (ASHRAE, SMACNA or the maker).

Results

Each C must refer to the velocity used here; tables sometimes base it on the branch or the outlet.

Velocity pressure8.4433mmWC
Sum of coefficients5.3000
Fitting losses44.749mmWC

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Typical branch at 8 m/s. The inputs, in the units selected above:

InputValue
Air velocity8.0000 m/s
Air density1.2000 kg/m³
Fitting 1: loss coefficient0.25000 -
Fitting 1: number4.0000 -
Fitting 2: loss coefficient0.60000 -
Fitting 2: number2.0000 -
Fitting 3: loss coefficient1.0000 -
Fitting 3: number1.0000 -
Fitting 4: loss coefficient0.30000 -
Fitting 4: number2.0000 -
Fitting 5: loss coefficient0 -
Fitting 5: number0 -
Fitting 6: loss coefficient0 -
Fitting 6: number0 -

Applying the formula below gives:

ResultValue
Velocity pressure3.9157 mmWC
Sum of coefficients3.8000
Fitting losses14.880 mmWC

Open this example in the calculator and change any input.

Formula

\(\Delta p = \left(\sum n_i C_i\right)\frac{\rho v^2}{2}\)

Variables

Symbol Meaning SI unit
\(v\) Air velocity m/s
\(\rho\) Air density kg/m³
\(C_{1}\) Fitting 1: loss coefficient -
\(n_{1}\) Fitting 1: number -
\(C_{2}\) Fitting 2: loss coefficient -
\(n_{2}\) Fitting 2: number -
\(C_{3}\) Fitting 3: loss coefficient -
\(n_{3}\) Fitting 3: number -
\(C_{4}\) Fitting 4: loss coefficient -
\(n_{4}\) Fitting 4: number -
\(C_{5}\) Fitting 5: loss coefficient -
\(n_{5}\) Fitting 5: number -
\(C_{6}\) Fitting 6: loss coefficient -
\(n_{6}\) Fitting 6: number -
\(p_v\) Velocity pressure Pa
\(\Sigma nC\) Sum of coefficients -
\(\Delta p\) Fitting losses Pa

Method and standards

Loss coefficient method.

Where it is used

  • Fan selection.
  • Checking duct systems.

Common mistakes

  • C referred to the wrong velocity.
  • Forgetting the system effect at the fan.

Assumptions and limits

  • Fittings far enough apart.
  • Numbers of fittings must be whole.

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 21 (duct design: dynamic losses Δp = C p_v)

Questions and answers

Four elbows at 0.25, two at 0.6, a damper at 1.0 and two transitions at 0.3, at 8 m/s?

ΣC 3.8: about 146 Pa.

Where are the C values?

ASHRAE fitting database, SMACNA or the maker.

And straight duct?

Add the friction loss from the duct pressure drop calculator.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.