FireCADCalc

Fan Power and Specific Fan Power (SFP) of an Air Handler

Fan electrical power from air flow and total pressure rise with fan, motor and drive efficiencies, the specific fan power and the annual energy and cost.

Food, dairy and textile

Inputs

Examples: Illustrative 5 m3/s at 900 PaEC fan unit 2 m3/s at 600 PaOld belt drive 10 m3/s at 1500 Pa

Accepted: 36 to 1,800,000 m³/h
Accepted: 10 to 10,000 Pa
Accepted: 20 to 95 %
Accepted: 50 to 100 %
Accepted: 50 to 100 %
Accepted: 0 to 8,760 h
Accepted: 0 to 100

Results

P = V̇Δp/(η_fη_mη_d); SFP = P/V̇ (1 kW per m³/s = 1 W per L/s). Good modern supply-and-extract units reach about 1.5–2 kW/(m³/s) in total; low pressure drop across filters, coils and ducts is the main lever.

Air power15.000kW
Electrical power30.864kW
Specific fan power (kW per m³/s = W per L/s)3.0864kJ/m³
Annual energy185.19MWh
Annual cost18,519

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 5 m3/s at 900 Pa. The inputs, in the units selected above:

InputValue
Air flow18,000 m³/h
Total pressure rise900.00 Pa
Fan efficiency70.000 %
Motor efficiency93.000 %
Drive (belt or VFD) efficiency95.000 %
Operating hours per year4,000.0 h
Electricity price per kWh0.12000 -

Applying the formula below gives:

ResultValue
Air power4.5000 kW
Electrical power7.2763 kW
Specific fan power (kW per m³/s = W per L/s)1.4553 kJ/m³
Annual energy29.105 MWh
Annual cost3,492.6

Open this example in the calculator and change any input.

Formula

\(P_e = \frac{\dot V\Delta p}{\eta_f\eta_m\eta_d}, \quad SFP = \frac{P_e}{\dot V}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow m³/s
\(\Delta p\) Total pressure rise Pa
\(\eta_f\) Fan efficiency -
\(\eta_m\) Motor efficiency -
\(\eta_d\) Drive (belt or VFD) efficiency -
\(t\) Operating hours per year s
\(c_e\) Electricity price per kWh -
\(P_a\) Air power W
\(P_e\) Electrical power W
\(SFP\) Specific fan power (kW per m³/s = W per L/s) J/m³
\(E\) Annual energy J
\(C\) Annual cost -

Method and standards

Fan power.

Where it is used

  • AHU selection and energy audits.
  • Comparing filter and coil options.

Common mistakes

  • Using static instead of total pressure.
  • Forgetting drive and motor losses.

Assumptions and limits

  • Steady operating point.

References

  • Fan power and specific fan power
  • CIBSE Guide A
  • Environmental Design (CIBSE)

Questions and answers

What SFP is good?

About 1–1.5 W/(L/s) per fan for efficient central systems; old belt-driven systems can exceed 3.

Where does the pressure go?

Typically filters, coils and heat recovery in the unit take half or more; ductwork and terminals the rest.

What do the defaults represent?

An illustrative 5 m³/s air handler at 900 Pa total pressure, 70 % fan, 93 % motor and 95 % drive efficiency, 4,000 hours a year.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.