Worked example
Example: Illustrative 5 m3/s at 900 Pa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow | 18,000 m³/h |
| Total pressure rise | 900.00 Pa |
| Fan efficiency | 70.000 % |
| Motor efficiency | 93.000 % |
| Drive (belt or VFD) efficiency | 95.000 % |
| Operating hours per year | 4,000.0 h |
| Electricity price per kWh | 0.12000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air power | 4.5000 kW |
| Electrical power | 7.2763 kW |
| Specific fan power (kW per m³/s = W per L/s) | 1.4553 kJ/m³ |
| Annual energy | 29.105 MWh |
| Annual cost | 3,492.6 |
Open this example in the calculator and change any input.
Formula
\(P_e = \frac{\dot V\Delta p}{\eta_f\eta_m\eta_d}, \quad SFP = \frac{P_e}{\dot V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow | m³/s |
| \(\Delta p\) | Total pressure rise | Pa |
| \(\eta_f\) | Fan efficiency | - |
| \(\eta_m\) | Motor efficiency | - |
| \(\eta_d\) | Drive (belt or VFD) efficiency | - |
| \(t\) | Operating hours per year | s |
| \(c_e\) | Electricity price per kWh | - |
| \(P_a\) | Air power | W |
| \(P_e\) | Electrical power | W |
| \(SFP\) | Specific fan power (kW per m³/s = W per L/s) | J/m³ |
| \(E\) | Annual energy | J |
| \(C\) | Annual cost | - |
Method and standards
Fan power.
Where it is used
- AHU selection and energy audits.
- Comparing filter and coil options.
Common mistakes
- Using static instead of total pressure.
- Forgetting drive and motor losses.
Assumptions and limits
- Steady operating point.
References
- Fan power and specific fan power
- CIBSE Guide A
- Environmental Design (CIBSE)
Questions and answers
What SFP is good?
About 1–1.5 W/(L/s) per fan for efficient central systems; old belt-driven systems can exceed 3.
Where does the pressure go?
Typically filters, coils and heat recovery in the unit take half or more; ductwork and terminals the rest.
What do the defaults represent?
An illustrative 5 m³/s air handler at 900 Pa total pressure, 70 % fan, 93 % motor and 95 % drive efficiency, 4,000 hours a year.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.