Condenser Water Flow and Heat Rejection of a Chiller

Heat rejected by a water-cooled chiller and the condenser water flow for a cooling tower range, from cooling capacity and COP, with water from IF97.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)Refrigeration and air-conditioning mechanic examinations

Inputs

Examples: 500 TR at COP 5.6, 29 to 34.5 °C100 TR at COP 4, 32 to 37 °C

Results

Heat rejected is cooling plus compressor input; motor losses of an open-drive machine stay in the plant room.

Heat rejected2,072.4kW
Condenser water mass flow324.59t/h
Volume flow (at the inlet)325.89m³/h
Flow per TR0.18105L/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 TR at COP 5.6, 29 to 34.5 °C. The inputs, in the units selected above:

InputValue
Cooling capacity500.00 TR
Chiller COP5.6000 -
Condenser water in (from the tower)29.000 °C
Condenser water out (to the tower)34.500 °C

Applying the formula below gives:

ResultValue
Heat rejected2,072.4 kW
Condenser water mass flow324.59 t/h
Volume flow (at the inlet)325.89 m³/h
Flow per TR0.18105 L/s

Open this example in the calculator and change any input.

Formula

\(\dot Q_r = \dot Q_e\left(1 + \frac{1}{COP}\right), \quad \dot m = \frac{\dot Q_r}{h_{out} - h_{in}}\)

Variables

Symbol Meaning SI unit
\(\dot Q_e\) Cooling capacity W
\(COP\) Chiller COP -
\(T_{in}\) Condenser water in (from the tower) K
\(T_{out}\) Condenser water out (to the tower) K
\(\dot Q_r\) Heat rejected W
\(\dot m\) Condenser water mass flow kg/s
\(\dot V\) Volume flow (at the inlet) m³/s
\(\dot V/TR\) Flow per TR m³/s

Method and standards

Energy balance.

Where it is used

  • Cooling tower and condenser pump sizing.
  • Chiller plant design.

Common mistakes

  • Using chilled water flow for the tower.
  • COP of the plant instead of the chiller.

Assumptions and limits

  • Steady state.
  • Water enthalpy and density from IAPWS-IF97 at 3 bar(a), a typical condenser-water pressure; the effect of pressure on liquid water is negligible here.

References

  • Energy balance Q_r = Q_e(1 + 1/COP); water enthalpies from IAPWS-IF97

Questions and answers

500 TR at COP 5.6 with a 5.5 K range?

About 2,070 kW rejected: roughly 325 m³/h of condenser water.

Why more than the chilled water flow?

The tower also removes the compressor's energy.

Larger range?

Less water and smaller pumps, but a higher condensing temperature.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.