Chilled Water Thermal Storage Tank Size

Volume, mass and diameter of a stratified chilled water storage tank for a cooling energy, from the temperature difference and the tank figure of merit.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)Tank and drumAir conditioning and chillers

Inputs

Examples: 5 000 kWh, 8 K, 8 °C mean, FOM 0.9, 10 m2 000 TR·h, 10 K, 9 °C, FOM 0.85, 12 m800 kWh, 6 K, 7 °C, FOM 0.9, 5 m

Results

Water properties from IAPWS-IF97 at 1 atm. Add volume for the diffusers, the thermocline and free board.

Water density at the mean temperature999.90kg/m³
Water specific heat at the mean temperature4.2007kJ/(kg·K)
Water mass126.96t
Water volume126.98m³
Inside diameter for the water height5.6863m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 000 kWh, 8 K, 8 °C mean, FOM 0.9, 10 m. The inputs, in the units selected above:

InputValue
Cooling energy to store5,000.0 kWh
Return minus supply temperature8.0000 K
Mean water temperature8.0000 °C
Figure of merit (usable share of the theoretical capacity)90.000 %
Water height in the tank10.000 m

Applying the formula below gives:

ResultValue
Water density at the mean temperature999.85 kg/m³
Water specific heat at the mean temperature4.1988 kJ/(kg·K)
Water mass595.41 t
Water volume595.50 m³
Inside diameter for the water height8.7075 m

Open this example in the calculator and change any input.

Formula

\(m = \frac{E}{c_p\, \Delta T\, FOM}, \quad V = \frac{m}{\rho}, \quad D = \sqrt{\frac{4V}{\pi H}}\)

Variables

Symbol Meaning SI unit
\(E\) Cooling energy to store J
\(\Delta T\) Return minus supply temperature K
\(T_m\) Mean water temperature K
\(FOM\) Figure of merit (usable share of the theoretical capacity) -
\(H\) Water height in the tank m
\(\rho\) Water density at the mean temperature kg/m³
\(c_p\) Water specific heat at the mean temperature J/(kg·K)
\(m\) Water mass kg
\(V\) Water volume m³
\(D\) Inside diameter for the water height m

Method and standards

Sensible storage in water; density and specific heat at the mean temperature from IAPWS-IF97.

Where it is used

  • Load shifting to off-peak tariff hours.
  • Reducing chiller size for peaky loads.
  • Process cooling buffers.

Common mistakes

  • Using the chiller ΔT instead of the achievable storage ΔT.
  • Forgetting the thermocline volume.
  • Ignoring heat gain through the tank wall.

Assumptions and limits

  • Stratified tank; liquid water at 1 atm.

References

  • Sensible heat storage
  • E = m cp ΔT (ASHRAE Handbook—HVAC Systems and Equipment, Thermal storage)
  • IAPWS-IF97 water properties

Questions and answers

How big a tank stores 5 000 kWh of cooling at 8 K?

About 595 m³ with a figure of merit of 0.9; 10 m of water needs an 8.7 m diameter.

Why does ΔT matter so much?

Volume falls in proportion to ΔT; a 10 K design needs 20 % less tank than 8 K.

What is the figure of merit?

The share of the theoretical capacity actually recovered; the thermocline and mixing take the rest. 0.85 to 0.9 is usual for good diffusers.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.