Worked example
Example: 5 000 kWh, 8 K, 8 °C mean, FOM 0.9, 10 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling energy to store | 5,000.0 kWh |
| Return minus supply temperature | 8.0000 K |
| Mean water temperature | 8.0000 °C |
| Figure of merit (usable share of the theoretical capacity) | 90.000 % |
| Water height in the tank | 10.000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water density at the mean temperature | 999.85 kg/m³ |
| Water specific heat at the mean temperature | 4.1988 kJ/(kg·K) |
| Water mass | 595.41 t |
| Water volume | 595.50 m³ |
| Inside diameter for the water height | 8.7075 m |
Open this example in the calculator and change any input.
Formula
\(m = \frac{E}{c_p\, \Delta T\, FOM}, \quad V = \frac{m}{\rho}, \quad D = \sqrt{\frac{4V}{\pi H}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | Cooling energy to store | J |
| \(\Delta T\) | Return minus supply temperature | K |
| \(T_m\) | Mean water temperature | K |
| \(FOM\) | Figure of merit (usable share of the theoretical capacity) | - |
| \(H\) | Water height in the tank | m |
| \(\rho\) | Water density at the mean temperature | kg/m³ |
| \(c_p\) | Water specific heat at the mean temperature | J/(kg·K) |
| \(m\) | Water mass | kg |
| \(V\) | Water volume | m³ |
| \(D\) | Inside diameter for the water height | m |
Method and standards
Sensible storage in water; density and specific heat at the mean temperature from IAPWS-IF97.
Where it is used
- Load shifting to off-peak tariff hours.
- Reducing chiller size for peaky loads.
- Process cooling buffers.
Common mistakes
- Using the chiller ΔT instead of the achievable storage ΔT.
- Forgetting the thermocline volume.
- Ignoring heat gain through the tank wall.
Assumptions and limits
- Stratified tank; liquid water at 1 atm.
References
- Sensible heat storage
- E = m cp ΔT (ASHRAE Handbook—HVAC Systems and Equipment, Thermal storage)
- IAPWS-IF97 water properties
Questions and answers
How big a tank stores 5 000 kWh of cooling at 8 K?
About 595 m³ with a figure of merit of 0.9; 10 m of water needs an 8.7 m diameter.
Why does ΔT matter so much?
Volume falls in proportion to ΔT; a 10 K design needs 20 % less tank than 8 K.
What is the figure of merit?
The share of the theoretical capacity actually recovered; the thermocline and mixing take the rest. 0.85 to 0.9 is usual for good diffusers.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.