Battery Capacity Converter (Ah, Wh, kWh)

Converts battery capacity in ampere-hours at a nominal voltage to stored and usable energy, with specific energy and runtime at a chosen load power.

Inputs

Examples: Illustrative 100 Ah 51.2 V LFP battery12 V 200 Ah lead-acid at 50 %Phone cell 4,500 mAh at 3.85 V

Accepted: 2.778E-10 to 277,780,000 Ah
Accepted: 0.1 to 100,000 V
Accepted: 1 to 100 %
Accepted: 1E-6 to 1E+9 kg
Accepted: 1E-9 to 1E+9 kW

Results

Energy is charge times voltage: E[Wh] = Q[Ah] × V_n. The nominal voltage is the average over a discharge (3.2 V per LFP cell, 3.6–3.7 V for NMC, 2.0 V for lead-acid), so the result is a rated figure. Usable energy depends on the permitted depth of discharge; real runtime is also cut by inverter losses, temperature and the discharge rate (Peukert effect for lead-acid).

Stored energy0.017325kWh
Usable energy0.017325kWh
Specific energy247.50Wh/kg
Runtime at the load6.9300h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 100 Ah 51.2 V LFP battery. The inputs, in the units selected above:

InputValue
Rated capacity100.00 Ah
Nominal voltage51.200 V
Usable depth of discharge90.000 %
Battery mass45.000 kg
Load power0.80000 kW

Applying the formula below gives:

ResultValue
Stored energy5.1200 kWh
Usable energy4.6080 kWh
Specific energy113.78 Wh/kg
Runtime at the load5.7600 h

Open this example in the calculator and change any input.

Formula

\(E = QV_n, \quad E_u = E\cdot DoD, \quad t = \frac{E_u}{P_L}\)

Variables

Symbol Meaning SI unit
\(Q\) Rated capacity C
\(V_n\) Nominal voltage V
\(DoD\) Usable depth of discharge -
\(m\) Battery mass kg
\(P_L\) Load power W
\(E\) Stored energy J
\(E_u\) Usable energy J
\(e_m\) Specific energy J/kg
\(t\) Runtime at the load s

Method and standards

Ah to Wh.

Where it is used

  • Comparing batteries with different voltages.
  • UPS, solar and EV battery sizing.

Common mistakes

  • Using full-charge voltage.
  • Ignoring depth of discharge and conversion losses.

Assumptions and limits

  • Nominal voltage constant over the discharge; no rate effects.

References

  • Energy = capacity × nominal voltage

Questions and answers

Why does a 100 Ah 12 V and a 100 Ah 48 V battery differ?

Energy scales with voltage: the 48 V pack holds four times as much.

What voltage should I use?

The nominal voltage on the label, not the full-charge voltage.

What do the defaults represent?

An illustrative 100 Ah, 51.2 V (16-cell LFP) battery of 45 kg, 90 % usable, supplying 800 W.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Linden and Reddy, Handbook of Batteries, 4th ed. (McGraw-Hill, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.