Worked example
Example: Illustrative 100 Ah 51.2 V LFP battery. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated capacity | 100.00 Ah |
| Nominal voltage | 51.200 V |
| Usable depth of discharge | 90.000 % |
| Battery mass | 45.000 kg |
| Load power | 0.80000 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Stored energy | 5.1200 kWh |
| Usable energy | 4.6080 kWh |
| Specific energy | 113.78 Wh/kg |
| Runtime at the load | 5.7600 h |
Open this example in the calculator and change any input.
Formula
\(E = QV_n, \quad E_u = E\cdot DoD, \quad t = \frac{E_u}{P_L}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Rated capacity | C |
| \(V_n\) | Nominal voltage | V |
| \(DoD\) | Usable depth of discharge | - |
| \(m\) | Battery mass | kg |
| \(P_L\) | Load power | W |
| \(E\) | Stored energy | J |
| \(E_u\) | Usable energy | J |
| \(e_m\) | Specific energy | J/kg |
| \(t\) | Runtime at the load | s |
Method and standards
Ah to Wh.
Where it is used
- Comparing batteries with different voltages.
- UPS, solar and EV battery sizing.
Common mistakes
- Using full-charge voltage.
- Ignoring depth of discharge and conversion losses.
Assumptions and limits
- Nominal voltage constant over the discharge; no rate effects.
References
- Energy = capacity × nominal voltage
Questions and answers
Why does a 100 Ah 12 V and a 100 Ah 48 V battery differ?
Energy scales with voltage: the 48 V pack holds four times as much.
What voltage should I use?
The nominal voltage on the label, not the full-charge voltage.
What do the defaults represent?
An illustrative 100 Ah, 51.2 V (16-cell LFP) battery of 45 kg, 90 % usable, supplying 800 W.