Worked example
Example: Illustrative 60 m2 wall: 650 W/m2, 1.6 mm holes on 20 mm, 0.03 kg/(m2 s), 5 C ambient. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Collector area | 60.000 m² |
| Solar radiation on the collector | 650.00 W/m² |
| Solar absorptance | 94.000 % |
| Infrared emittance | 90.000 % |
| Suction mass flux | 108.00 kg/(m²·h) |
| Hole diameter | 1.6000 mm |
| Hole pitch (equilateral triangles) | 20.000 mm |
| Ambient temperature | 5.0000 °C |
| Sky temperature | -5.0000 °C |
| View factor to the ground (0.5 for a vertical wall) | 50.000 % |
| Air density | 1.2700 kg/m³ |
| Air conductivity | 0.024500 W/(m·K) |
| Air specific heat | 1.0060 kJ/(kg·K) |
| Air viscosity | 0.017500 mPa·s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Porosity (hole area share) | 0.58042 % |
| Velocity in the holes | 4.0698 m/s |
| Hole Reynolds number | 472.57 |
| Heat transfer coefficient | 28.715 W/(m²·K) |
| Number of transfer units | 0.94593 |
| Absorber temperature | 30.130 °C |
| Useful gain | 27.835 kW |
| Outlet air temperature | 20.372 °C |
| Collector efficiency | 71.372 % |
Open this example in the calculator and change any input.
Formula
\(Nu_D = \frac{hD}{k} = 2.75\left(\frac{P}{D}\right)^{-1.2}Re_D^{0.43}, \quad NTU = \frac{h(A_c - A_h)}{\dot mc_p}\)
\(\alpha G_T - \varepsilon\sigma\left[F_{c-g}(T_c^4 - T_a^4) + (1 - F_{c-g})(T_c^4 - T_{sky}^4)\right] = \frac{\dot m}{A_c}c_p(T_c - T_a)(1 - e^{-NTU})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_c\) | Collector area | m² |
| \(G_T\) | Solar radiation on the collector | W/m² |
| \(\alpha\) | Solar absorptance | - |
| \(\varepsilon\) | Infrared emittance | - |
| \(\dot m/A_c\) | Suction mass flux | kg/(m²·s) |
| \(D\) | Hole diameter | m |
| \(P\) | Hole pitch (equilateral triangles) | m |
| \(T_a\) | Ambient temperature | K |
| \(T_{sky}\) | Sky temperature | K |
| \(F_{c-g}\) | View factor to the ground (0.5 for a vertical wall) | - |
| \(\rho\) | Air density | kg/m³ |
| \(k\) | Air conductivity | W/(m·K) |
| \(c_p\) | Air specific heat | J/(kg·K) |
| \(\mu\) | Air viscosity | Pa·s |
| \(\sigma\) | Porosity (hole area share) | - |
| \(V_h\) | Velocity in the holes | m/s |
| \(Re_D\) | Hole Reynolds number | - |
| \(h\) | Heat transfer coefficient | W/(m²·K) |
| \(NTU\) | Number of transfer units | - |
| \(T_c\) | Absorber temperature | K |
| \(Q_u\) | Useful gain | W |
| \(T_o\) | Outlet air temperature | K |
| \(\eta\) | Collector efficiency | - |
Method and standards
Energy balance of a perforated absorber with suction and radiative loss.
Where it is used
- Ventilation air preheating on industrial walls.
- Crop drying air.
Common mistakes
- Adding a glazing loss coefficient to an unglazed wall.
- Using a suction rate so low that wind loss returns.
Assumptions and limits
- Uniform suction; wind effects neglected; steady state.
References
- Kutscher's hole heat transfer correlation with a radiation-only loss and ε-NTU suction heat transfer
Questions and answers
Why is there no glazing?
Air drawn through the holes sweeps the warm boundary layer into the collector, so convective loss is almost eliminated and only radiation remains.
What suction rate is used?
About 0.01–0.05 kg/(m²·s) (roughly 30–150 m³/h per m²); lower flow gives warmer air but lower efficiency.
What do the defaults represent?
An illustrative 60 m² wall, 650 W/m², 1.6 mm holes on 20 mm pitch, 0.03 kg/(m²·s) suction at 5 °C ambient and a −5 °C sky.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 6.14, eqs. 6.14.9 to 6.14.11 and Example 6.14.2