Unglazed Transpired Solar Air Collector: Temperature and Gain

Absorber temperature, useful gain, outlet air temperature and efficiency of a perforated (transpired) solar air heating wall from hole geometry and suction rate.

Food, dairy and textile

Inputs

Examples: Illustrative 60 m2 wall: 650 W/m2, 1.6 mm holes on 20 mm, 0.03 kg/(m2 s), 5 C ambientLow suction 0.015 kg/(m2 s) on a cold clear day

Accepted: 0.5 to 10,000 m²
Accepted: 10 to 1,200 W/m²
Accepted: 50 to 100 %
Accepted: 5 to 100 %
Accepted: 18 to 720 kg/(m²·h)
Accepted: 0.5 to 10 mm
Accepted: 5 to 100 mm
Accepted: -43.15 to 56.85 °C
Accepted: -73.15 to 46.85 °C
Accepted: 0 to 100 %
Accepted: 0.8 to 1.5 kg/m³
Accepted: 0.02 to 0.035 W/(m·K)
Accepted: 0.99 to 1.02 kJ/(kg·K)
Accepted: 0.015 to 0.022 mPa·s

Results

Kutscher's correlation Nu_D = 2.75 (P/D)^−1.2 Re_D^0.43 for the plate-to-air coefficient; the absorber loses heat by radiation only (no wind convection, valid at suction fluxes high enough to keep the boundary layer attached).

Porosity (hole area share)0.58042%
Velocity in the holes4.0698m/s
Hole Reynolds number472.57
Heat transfer coefficient28.715W/(m²·K)
Number of transfer units0.94593
Absorber temperature30.130°C
Useful gain27.835kW
Outlet air temperature20.372°C
Collector efficiency71.372%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 60 m2 wall: 650 W/m2, 1.6 mm holes on 20 mm, 0.03 kg/(m2 s), 5 C ambient. The inputs, in the units selected above:

InputValue
Collector area60.000 m²
Solar radiation on the collector650.00 W/m²
Solar absorptance94.000 %
Infrared emittance90.000 %
Suction mass flux108.00 kg/(m²·h)
Hole diameter1.6000 mm
Hole pitch (equilateral triangles)20.000 mm
Ambient temperature5.0000 °C
Sky temperature-5.0000 °C
View factor to the ground (0.5 for a vertical wall)50.000 %
Air density1.2700 kg/m³
Air conductivity0.024500 W/(m·K)
Air specific heat1.0060 kJ/(kg·K)
Air viscosity0.017500 mPa·s

Applying the formula below gives:

ResultValue
Porosity (hole area share)0.58042 %
Velocity in the holes4.0698 m/s
Hole Reynolds number472.57
Heat transfer coefficient28.715 W/(m²·K)
Number of transfer units0.94593
Absorber temperature30.130 °C
Useful gain27.835 kW
Outlet air temperature20.372 °C
Collector efficiency71.372 %

Open this example in the calculator and change any input.

Formula

\(Nu_D = \frac{hD}{k} = 2.75\left(\frac{P}{D}\right)^{-1.2}Re_D^{0.43}, \quad NTU = \frac{h(A_c - A_h)}{\dot mc_p}\)

\(\alpha G_T - \varepsilon\sigma\left[F_{c-g}(T_c^4 - T_a^4) + (1 - F_{c-g})(T_c^4 - T_{sky}^4)\right] = \frac{\dot m}{A_c}c_p(T_c - T_a)(1 - e^{-NTU})\)

Variables

Symbol Meaning SI unit
\(A_c\) Collector area m²
\(G_T\) Solar radiation on the collector W/m²
\(\alpha\) Solar absorptance -
\(\varepsilon\) Infrared emittance -
\(\dot m/A_c\) Suction mass flux kg/(m²·s)
\(D\) Hole diameter m
\(P\) Hole pitch (equilateral triangles) m
\(T_a\) Ambient temperature K
\(T_{sky}\) Sky temperature K
\(F_{c-g}\) View factor to the ground (0.5 for a vertical wall) -
\(\rho\) Air density kg/m³
\(k\) Air conductivity W/(m·K)
\(c_p\) Air specific heat J/(kg·K)
\(\mu\) Air viscosity Pa·s
\(\sigma\) Porosity (hole area share) -
\(V_h\) Velocity in the holes m/s
\(Re_D\) Hole Reynolds number -
\(h\) Heat transfer coefficient W/(m²·K)
\(NTU\) Number of transfer units -
\(T_c\) Absorber temperature K
\(Q_u\) Useful gain W
\(T_o\) Outlet air temperature K
\(\eta\) Collector efficiency -

Method and standards

Energy balance of a perforated absorber with suction and radiative loss.

Where it is used

  • Ventilation air preheating on industrial walls.
  • Crop drying air.

Common mistakes

  • Adding a glazing loss coefficient to an unglazed wall.
  • Using a suction rate so low that wind loss returns.

Assumptions and limits

  • Uniform suction; wind effects neglected; steady state.

References

  • Kutscher's hole heat transfer correlation with a radiation-only loss and ε-NTU suction heat transfer

Questions and answers

Why is there no glazing?

Air drawn through the holes sweeps the warm boundary layer into the collector, so convective loss is almost eliminated and only radiation remains.

What suction rate is used?

About 0.01–0.05 kg/(m²·s) (roughly 30–150 m³/h per m²); lower flow gives warmer air but lower efficiency.

What do the defaults represent?

An illustrative 60 m² wall, 650 W/m², 1.6 mm holes on 20 mm pitch, 0.03 kg/(m²·s) suction at 5 °C ambient and a −5 °C sky.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 6.14, eqs. 6.14.9 to 6.14.11 and Example 6.14.2

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.