Fully Mixed Solar Storage Tank Temperature After a Period

Temperature of a fully mixed hot-water storage tank after a period with solar gain, load withdrawal and losses to its surroundings, by Euler step and exact solution.

Process steam and utilitiesFood, dairy and textile

Inputs

Examples: Overnight 14 h standing loss: 300 L tank at 60 C, UA 2 W/K, 15 CPerfectly insulated tank, 2 m3, 5 h, 120 MJ in, 40 MJ out

Accepted: 1 to 100,000,000 kg
Accepted: 0.5 to 5 kJ/(kg·K)
Accepted: 0 to 1,000 kW/K
Accepted: -43.15 to 56.85 °C
Accepted: 0 to 126.85 °C
Accepted: 0 to 10,000,000 MJ
Accepted: 0 to 10,000,000 MJ
Accepted: 0.016667 to 2,777.8 h

Results

A fully mixed tank; real tanks stratify, which keeps the collector inlet cooler and the load supply hotter.

Tank loss during the period (Euler)4.5360MJ
Final temperature, one Euler step56.383°C
Final temperature, exact for steady rates56.524°C
Temperature the tank would settle at15.000°C
Tank time constant M c_p/(UA)174.17h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Overnight 14 h standing loss: 300 L tank at 60 C, UA 2 W/K, 15 C. The inputs, in the units selected above:

InputValue
Mass of water in the tank300.00 kg
Specific heat4.1800 kJ/(kg·K)
Tank loss coefficient-area product0.002000 kW/K
Temperature around the tank15.000 °C
Tank temperature at the start60.000 °C
Solar energy added during the period0 MJ
Energy removed to the load during the period0 MJ
Period14.000 h

Applying the formula below gives:

ResultValue
Tank loss during the period (Euler)4.5360 MJ
Final temperature, one Euler step56.383 °C
Final temperature, exact for steady rates56.524 °C
Temperature the tank would settle at15.000 °C
Tank time constant M c_p/(UA)174.17 h

Open this example in the calculator and change any input.

Formula

\(T_s^+ = T_s + \frac{\Delta t}{(Mc_p)_s}\left[Q_u - L_s - (UA)_s(T_s - T'_a)\right]\)

\(T_s(\Delta t) = T_\infty + (T_s - T_\infty)e^{-\Delta t(UA)_s/(Mc_p)_s}, \quad T_\infty = T'_a + \frac{(Q_u - L_s)/\Delta t}{(UA)_s}\)

Variables

Symbol Meaning SI unit
\(M\) Mass of water in the tank kg
\(c_p\) Specific heat J/(kg·K)
\((UA)_s\) Tank loss coefficient-area product W/K
\(T'_a\) Temperature around the tank K
\(T_s\) Tank temperature at the start K
\(Q_u\) Solar energy added during the period J
\(L_s\) Energy removed to the load during the period J
\(\Delta t\) Period s
\(Q_{loss}\) Tank loss during the period (Euler) J
\(T_s^+\) Final temperature, one Euler step K
\(T_s(\Delta t)\) Final temperature, exact for steady rates K
\(T_\infty\) Temperature the tank would settle at K
\(\tau\) Tank time constant M c_p/(UA) s

Method and standards

Energy balance of a fully mixed (unstratified) storage tank.

Where it is used

  • Hour-by-hour solar system simulation by hand.
  • Overnight temperature drop of a hot-water store.

Common mistakes

  • Mixing energy over the period with power.
  • Using a long step that overshoots the surrounding temperature.

Assumptions and limits

  • Fully mixed; constant gain and load rates over the period for the exact solution.

Questions and answers

When is one Euler step enough?

When the period is short compared with the tank time constant M c_p/(UA), usually days for a well-insulated tank; the exact solution is shown for comparison.

How much storage is usual?

50 to 100 litres of water per m² of collector for space and water heating; the f-chart assumes 75 L/m².

What do the defaults represent?

An illustrative case: Overnight 14 h standing loss: 300 L tank at 60 C, UA 2 W/K, 15 C. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 8.3, eq. 8.3.3 and Example 8.3.1

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.