Worked example
Example: Water collector 2.5 m2, tested at 0.05 kg/s, used at 0.03 kg/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Temperature basis of the test parameters | Inlet temperature (F_R) |
| Test intercept (optical efficiency) | 75.000 % |
| Test slope (loss coefficient) | 5.0000 W/(m²·K) |
| Collector area the test parameters refer to | 2.5000 m² |
| Test flow rate | 0.050000 kg/s |
| Test fluid specific heat | 4.1870 kJ/(kg·K) |
| Flow rate in use | 0.030000 kg/s |
| Fluid specific heat in use | 4.1870 kJ/(kg·K) |
| Incidence angle modifier coefficient (0.1 one cover, 0.17 two) | 0.10000 - |
| Angle of incidence for the modifier | 45.000 ° |
Applying the formula below gives:
| Result | Value |
|---|---|
| Intercept on inlet basis at test flow | 75.000 % |
| Slope on inlet basis at test flow | 5.0000 W/(m²·K) |
| F'U_L from the test | 5.1555 W/(m²·K) |
| Flow-rate correction ratio | 0.97996 |
| Intercept at the use flow rate | 73.497 % |
| Slope at the use flow rate | 4.8998 W/(m²·K) |
| Incidence angle modifier | 0.95858 |
Open this example in the calculator and change any input.
Formula
\(F_R(\tau\alpha) = F_{av}(\tau\alpha)\left(1 + \frac{A_cF_{av}U_L}{2\dot mc_p}\right)^{-1}, \quad F_R(\tau\alpha) = F_o(\tau\alpha)\left(1 + \frac{A_cF_oU_L}{\dot mc_p}\right)^{-1}\)
\(F'U_L = -\frac{\dot mc_p}{A_c}\ln\left(1 - \frac{F_RU_LA_c}{\dot mc_p}\right), \quad r = \frac{\left.\frac{\dot mc_p}{A_cF'U_L}\left(1 - e^{-A_cF'U_L/\dot mc_p}\right)\right|_{use}}{\left.\frac{\dot mc_p}{A_cF'U_L}\left(1 - e^{-A_cF'U_L/\dot mc_p}\right)\right|_{test}}, \quad K_{\tau\alpha} = 1 - b_0\left(\frac{1}{\cos\theta} - 1\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{basis}\) | Temperature basis of the test parameters | - |
| \(F_x(\tau\alpha)_n\) | Test intercept (optical efficiency) | - |
| \(F_xU_L\) | Test slope (loss coefficient) | W/(m²·K) |
| \(A_c\) | Collector area the test parameters refer to | m² |
| \(\dot m_{test}\) | Test flow rate | kg/s |
| \(c_{p,test}\) | Test fluid specific heat | J/(kg·K) |
| \(\dot m_{use}\) | Flow rate in use | kg/s |
| \(c_{p,use}\) | Fluid specific heat in use | J/(kg·K) |
| \(b_0\) | Incidence angle modifier coefficient (0.1 one cover, 0.17 two) | - |
| \(\theta\) | Angle of incidence for the modifier | rad |
| \(F_R(\tau\alpha)_n\) | Intercept on inlet basis at test flow | - |
| \(F_RU_L\) | Slope on inlet basis at test flow | W/(m²·K) |
| \(F'U_L\) | F'U_L from the test | W/(m²·K) |
| \(r\) | Flow-rate correction ratio | - |
| \(F_R(\tau\alpha)_{n,use}\) | Intercept at the use flow rate | - |
| \(F_RU_{L,use}\) | Slope at the use flow rate | W/(m²·K) |
| \(K_{\tau\alpha}\) | Incidence angle modifier | - |
Method and standards
Conversion of collector test results between temperature bases and flow rates.
Where it is used
- Using manufacturers' test sheets in design methods.
- Assessing low-flow operation.
Common mistakes
- Mixing gross and aperture areas between the test and the design.
- Applying the liquid flow correction to air collectors.
Assumptions and limits
- Linear efficiency curve; F' independent of flow rate.
Questions and answers
Why convert to inlet basis?
Design methods such as the f-chart and the Hottel–Whillier equation use F_R with the inlet temperature, which is the quantity known in a system.
Does a lower flow rate always lose energy?
In the collector, yes: F_R falls. But low-flow systems keep the tank stratified, so the inlet temperature falls too and the system can gain overall.
What do the defaults represent?
An illustrative case: Water collector 2.5 m2, tested at 0.05 kg/s, used at 0.03 kg/s. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), secs. 6.17, 6.19 and 6.20, eqs. 6.17.10, 6.19.2 to 6.19.5 and 6.20.2 to 6.20.4, Examples 6.19.1, 6.19.2 and 6.20.1