Flat-Plate Collector Top Loss and Overall Loss Coefficient (Klein)

Top loss coefficient of a flat-plate solar collector by Klein's empirical equation, with back and edge losses giving the overall loss coefficient UL.

Process steam and utilitiesFood, dairy and textile

Inputs

Examples: Selective plate 0.10, one cover, 60 C, 20 C, wind 15Two covers, black plate, 80 C, 0 C, 75 deg (treated as 70)

Accepted: 1 to 3
Accepted: 2 to 100 %
Accepted: 50 to 100 %
Accepted: 0 to 90 °
Accepted: 6.85 to 226.85 °C
Accepted: -43.15 to 56.85 °C
Accepted: 1 to 100 W/(m²·K)
Accepted: 0.01 to 1 W/(m·K)
Accepted: 1 to 500 mm
Accepted: 0 to 10 W/(m²·K)

Results

Klein's equation reproduces the detailed cover-by-cover calculation within about 0.3 W/(m²·K) for plate temperatures from ambient to 200 °C, ambient −15 to 35 °C, wind 0–10 m/s, one to three covers and slopes 0–90°, for a plate-to-cover gap of about 25 mm.

Klein factor f0.90537
Klein factor C390.05
Klein exponent e0.30824
Top loss, convective part1.3303W/(m²·K)
Top loss, radiative part2.0124W/(m²·K)
Top loss coefficient3.3427W/(m²·K)
Back loss coefficient0.46667W/(m²·K)
Overall loss coefficient3.9094W/(m²·K)
Heat loss per unit area at these temperatures312.75W/m²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Selective plate 0.10, one cover, 60 C, 20 C, wind 15. The inputs, in the units selected above:

InputValue
Number of glass covers1.0000 -
Plate emittance (selective 0.1, black paint 0.95)10.000 %
Glass emittance88.000 %
Collector slope30.000 °
Mean plate temperature60.000 °C
Ambient temperature20.000 °C
Wind heat transfer coefficient (about 5.7 + 3.8V)15.000 W/(m²·K)
Back insulation conductivity0.040000 W/(m·K)
Back insulation thickness50.000 mm
Edge loss coefficient, referred to collector area0.20000 W/(m²·K)

Applying the formula below gives:

ResultValue
Klein factor f2.3300
Klein factor C496.13
Klein exponent e0.30093
Top loss, convective part2.6010 W/(m²·K)
Top loss, radiative part0.86340 W/(m²·K)
Top loss coefficient3.4644 W/(m²·K)
Back loss coefficient0.80000 W/(m²·K)
Overall loss coefficient4.4644 W/(m²·K)
Heat loss per unit area at these temperatures178.58 W/m²

Open this example in the calculator and change any input.

Formula

\(U_t = \left[\frac{N}{\frac{C}{T_{pm}}\left(\frac{T_{pm} - T_a}{N + f}\right)^e} + \frac{1}{h_w}\right]^{-1} + \frac{\sigma(T_{pm} + T_a)(T_{pm}^2 + T_a^2)}{(\varepsilon_p + 0.00591Nh_w)^{-1} + \frac{2N + f - 1 + 0.133\varepsilon_p}{\varepsilon_g} - N}\)

\(f = (1 + 0.089h_w - 0.1166h_w\varepsilon_p)(1 + 0.07866N), \quad C = 520(1 - 0.000051\beta^2), \quad e = 0.430\left(1 - \frac{100}{T_{pm}}\right), \quad U_L = U_t + \frac{k}{L} + U_e\)

Variables

Symbol Meaning SI unit
\(N\) Number of glass covers -
\(\varepsilon_p\) Plate emittance (selective 0.1, black paint 0.95) -
\(\varepsilon_g\) Glass emittance -
\(\beta\) Collector slope rad
\(T_{pm}\) Mean plate temperature K
\(T_a\) Ambient temperature K
\(h_w\) Wind heat transfer coefficient (about 5.7 + 3.8V) W/(m²·K)
\(k_b\) Back insulation conductivity W/(m·K)
\(L_b\) Back insulation thickness m
\(U_e\) Edge loss coefficient, referred to collector area W/(m²·K)
\(f\) Klein factor f -
\(C\) Klein factor C -
\(e\) Klein exponent e -
\(U_{t,conv}\) Top loss, convective part W/(m²·K)
\(U_{t,rad}\) Top loss, radiative part W/(m²·K)
\(U_t\) Top loss coefficient W/(m²·K)
\(U_b\) Back loss coefficient W/(m²·K)
\(U_L\) Overall loss coefficient W/(m²·K)
\(q_L\) Heat loss per unit area at these temperatures W/m²

Method and standards

Klein's empirical fit to the cover-by-cover top loss calculation.

Where it is used

  • Estimating U_L for collector design or when test data are missing.
  • Comparing one and two covers or a selective absorber.

Common mistakes

  • Entering temperatures in °C in the Klein equation (it needs kelvin).
  • Forgetting the back and edge losses.

Assumptions and limits

  • Plate-to-cover gap about 25 mm; slope above 70° treated as 70°.

Questions and answers

How much does a selective surface help?

Dropping the plate emittance from 0.95 to 0.10 roughly halves the top loss of a single-glazed collector at 100 °C, because radiation is about half of it.

What wind coefficient should I use?

McAdams' h = 5.7 + 3.8V (V in m/s) is widely used though it includes some radiation; Designers suggest h = max(5, 8.6V0.6/L0.4).

What do the defaults represent?

An illustrative case: Selective plate 0.10, one cover, 60 C, 20 C, wind 15. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 6.4, eq. 6.4.9 (Klein, 1979) and Example 6.4.2

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.