Collector Heat Exchanger Penalty Factor F'R/FR

Reduction in collector heat removal factor caused by a heat exchanger between an antifreeze collector loop and the tank, from exchanger effectiveness and flows.

Process steam and utilitiesFood, dairy and textile

Inputs

Examples: 40 m2 field, glycol 0.5 kg/s, water 0.4 kg/s, eff. 0.6Small exchanger, eff. 0.35, 6 m2

Accepted: 0.1 to 100,000 m²
Accepted: 0.1 to 30 W/(m²·K)
Accepted: 5 to 100 %
Accepted: 1E-5 to 1,000 kg/s
Accepted: 0.5 to 5 kJ/(kg·K)
Accepted: 1E-5 to 1,000 kg/s
Accepted: 0.5 to 5 kJ/(kg·K)
Accepted: 5 to 100 %

Results

The penalty acts as if the collector worked at a higher inlet temperature; a factor above about 0.95 is usual in good designs. Correct the collector for pipe losses first, then for the exchanger.

Collector-side capacitance rate280.00W/K
Minimum capacitance rate280.00W/K
Heat exchanger penalty factor83.404%
Intercept with the exchanger62.553%
Slope with the exchanger4.1702W/(m²·K)

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 40 m2 field, glycol 0.5 kg/s, water 0.4 kg/s, eff. 0.6. The inputs, in the units selected above:

InputValue
Collector area40.000 m²
Collector F_R U_L4.2000 W/(m²·K)
Collector F_R(τα)_n72.000 %
Collector-loop flow0.50000 kg/s
Collector-loop fluid specific heat3.6000 kJ/(kg·K)
Tank-side flow0.40000 kg/s
Tank-side fluid specific heat4.1800 kJ/(kg·K)
Heat exchanger effectiveness60.000 %

Applying the formula below gives:

ResultValue
Collector-side capacitance rate1,800.0 W/K
Minimum capacitance rate1,672.0 W/K
Heat exchanger penalty factor93.099 %
Intercept with the exchanger67.031 %
Slope with the exchanger3.9101 W/(m²·K)

Open this example in the calculator and change any input.

Formula

\(\frac{F'_R}{F_R} = \left[1 + \frac{A_cF_RU_L}{(\dot mc_p)_c}\left(\frac{(\dot mc_p)_c}{\varepsilon(\dot mc_p)_{min}} - 1\right)\right]^{-1}\)

Variables

Symbol Meaning SI unit
\(A_c\) Collector area m²
\(F_RU_L\) Collector F_R U_L W/(m²·K)
\(F_R(\tau\alpha)_n\) Collector F_R(τα)_n -
\(\dot m_c\) Collector-loop flow kg/s
\(c_{p,c}\) Collector-loop fluid specific heat J/(kg·K)
\(\dot m_s\) Tank-side flow kg/s
\(c_{p,s}\) Tank-side fluid specific heat J/(kg·K)
\(\varepsilon\) Heat exchanger effectiveness -
\((\dot mc_p)_c\) Collector-side capacitance rate W/K
\((\dot mc_p)_{min}\) Minimum capacitance rate W/K
\(F'_R/F_R\) Heat exchanger penalty factor -
\(F'_R(\tau\alpha)_n\) Intercept with the exchanger -
\(F'_RU_L\) Slope with the exchanger W/(m²·K)

Method and standards

De Winter's collector–heat exchanger factor.

Where it is used

  • Designing glycol solar loops.
  • f-chart input F'_R/F_R.

Common mistakes

  • Using the tank-side flow as the collector flow.
  • Applying the factor twice (once in F_R and again here).

Assumptions and limits

  • Steady state, constant effectiveness.

Questions and answers

Why include the heat exchanger at all?

Antifreeze loops protect the collectors from freezing; the price is a higher collector inlet temperature, which this factor expresses.

How can I reduce the penalty?

Larger effectiveness and balanced flows; the penalty also shrinks with a lower collector F_R U_L.

What do the defaults represent?

An illustrative case: 40 m2 field, glycol 0.5 kg/s, water 0.4 kg/s, eff. 0.6. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 10.2, eq. 10.2.3 (de Winter, 1975) and Example 10.2.1

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.