Liquid Hydrogen Tank Boil-Off

Boil-off rate of a liquid hydrogen tank from its heat leak, as kg per day and per cent of the full tank per day, with the hold time to empty.

Chemical and fertiliser

Inputs

Examples: Illustrative 50 m3 tank, 250 WLarge sphere 3200 m3, 4 kWSmall 1 m3 dewar, 20 W

Accepted: 1E-5 to 1,000 kW
Accepted: 0.01 to 1,000,000 m³
Accepted: 100 to 1,000 kJ/kg
Accepted: 50 to 90 kg/m³
Accepted: 5 to 100 %

Results

ṁ = Q/h_fg with all leaked heat evaporating liquid at constant pressure (vented tank). Small tanks lose 1–3 % a day, large spheres about 0.1 % a day because heat leak grows with surface and contents with volume. Ortho-para conversion adds heat in freshly liquefied hydrogen.

Boil-off rate0.16143kg/h
Boil-off per day3.8744kg
Boil-off per day (fraction of contents)6.8405%
Hydrogen in the tank56.640kg
Time to boil off the contents14.619d

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 50 m3 tank, 250 W. The inputs, in the units selected above:

InputValue
Heat leak into the tank0.25000 kW
Tank liquid volume50.000 m³
Latent heat of vaporisation (446 kJ/kg at 1 atm)446.00 kJ/kg
Liquid density (70.8 kg/m³ at 1 atm)70.800 kg/m³
Fill fraction90.000 %

Applying the formula below gives:

ResultValue
Boil-off rate2.0179 kg/h
Boil-off per day48.430 kg
Boil-off per day (fraction of contents)1.5201 %
Hydrogen in the tank3,186.0 kg
Time to boil off the contents65.785 d

Open this example in the calculator and change any input.

Formula

\(\dot m_b = \frac{\dot Q}{h_{fg}}, \quad \frac{\dot m_b\cdot 1\,d}{\rho_lVf}\)

Variables

Symbol Meaning SI unit
\(\dot Q\) Heat leak into the tank W
\(V\) Tank liquid volume m³
\(h_{fg}\) Latent heat of vaporisation (446 kJ/kg at 1 atm) J/kg
\(\rho_l\) Liquid density (70.8 kg/m³ at 1 atm) kg/m³
\(f\) Fill fraction -
\(\dot m_b\) Boil-off rate kg/s
\(\dot m_{day}\) Boil-off per day kg
\(\dot m/m\) Boil-off per day (fraction of contents) -
\(m\) Hydrogen in the tank kg
\(t_{empty}\) Time to boil off the contents s

Method and standards

Cryogenic boil-off.

Where it is used

  • Liquid hydrogen storage and transport.
  • Insulation specification.

Common mistakes

  • Ignoring ortho-para conversion heat.
  • Assuming a sealed tank (pressure would rise instead).

Assumptions and limits

  • Vented tank at constant pressure.

References

  • Boil-off energy balance of a cryogenic tank

Questions and answers

Why is boil-off unavoidable?

Liquid hydrogen sits at −253 °C; no insulation is perfect, and every 446 J of leaked heat evaporates a gram.

Why do big tanks lose a smaller fraction?

Heat leak scales with surface area but contents with volume, so the loss fraction falls roughly with tank diameter.

What do the defaults represent?

An illustrative 50 m³ tank, 90 % full, with a 250 W heat leak.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Larminie and Dicks, Fuel Cell Systems Explained, 2nd ed. (Wiley, 2003), ch. 8

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.