Electrolyser Stack Sizing: Current, Cells and Active Area

Stack current, number of cells and stacks and total active area of a water electrolyser from power, cell voltage, current density and cell area.

Chemical and fertiliser

Inputs

Examples: Illustrative 10 MW PEM, 2 A/cm2, 3000 cm2Alkaline 20 MW, 0.4 A/cm2, 2.7 m2Small 100 kW PEM, 1.5 A/cm2, 300 cm2

Accepted: 0.001 to 10,000 MW
Accepted: 1.2 to 3 V
Accepted: 0.01 to 5 A/cm²
Accepted: 1 to 100,000 cm²
Accepted: 1 to 1,000

Results

Cells in series carry the same current I = iA_c; N = P/(V_cI). PEM electrolysers run at 1–3 A/cm², alkaline at 0.2–0.5 A/cm², so alkaline stacks need several times more area for the same power.

Cell (stack) current6,000.0A
Cells needed878.00
Stacks4.0000
Total active area263.40m²
Stack voltage with full stacks418.00V
Power per active area37.965kW/m²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 10 MW PEM, 2 A/cm2, 3000 cm2. The inputs, in the units selected above:

InputValue
Electrolyser power10.000 MW
Cell voltage1.9000 V
Current density2.0000 A/cm²
Active area per cell3,000.0 cm²
Maximum cells per stack250.00 -

Applying the formula below gives:

ResultValue
Cell (stack) current6,000.0 A
Cells needed878.00
Stacks4.0000
Total active area263.40 m²
Stack voltage with full stacks418.00 V
Power per active area37.965 kW/m²

Open this example in the calculator and change any input.

Formula

\(I = iA_c, \quad N = \frac{P}{V_cI}, \quad n_s = \left\lceil\frac{N}{N_{max}}\right\rceil\)

Variables

Symbol Meaning SI unit
\(P\) Electrolyser power W
\(V_c\) Cell voltage V
\(i\) Current density A/m²
\(A_c\) Active area per cell m²
\(N_{max}\) Maximum cells per stack -
\(I\) Cell (stack) current A
\(N\) Cells needed -
\(n_s\) Stacks -
\(A_{tot}\) Total active area m²
\(V_{stack}\) Stack voltage with full stacks V
\(P/A\) Power per active area W/m²

Method and standards

Stack sizing.

Where it is used

  • Electrolyser plant layout and power supply design.
  • Comparing technologies.

Common mistakes

  • Mixing A/cm² and A/m².
  • Forgetting rectifier voltage limits.

Assumptions and limits

  • Uniform cells; constant current density.

References

  • Series stack arithmetic

Questions and answers

Why do PEM electrolysers use high current density?

Thin membranes and compact cells allow 2 A/cm² or more, reducing expensive catalyst-coated area per MW, at some cost in efficiency.

Why split into several stacks?

Stack voltage and cell count are limited by manufacturing, sealing and DC supply voltage; large plants use many stacks in parallel.

What do the defaults represent?

An illustrative 10 MW PEM electrolyser at 1.9 V and 2 A/cm² with 3,000 cm² cells and up to 250 cells per stack.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Larminie and Dicks, Fuel Cell Systems Explained, 2nd ed. (Wiley, 2003), ch. 8

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.