Worked example
Example: 10 000 Nm3/h toluene, 760 °C, RTO 95 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gas flow at 0 °C, 1 atm | 10,000 Nm³/h |
| Inlet gas temperature | 30.000 °C |
| Combustion chamber temperature | 760.00 °C |
| Chamber volume | 8.0000 m³ |
| Heat recovery effectiveness (0 none, 0.6–0.7 recuperative, 0.95 regenerative) | 95.000 % |
| Gas specific heat | 1.1000 kJ/(kg·K) |
| log₁₀ of the VOC rate constant A (1/s) | 13.358 - |
| Activation energy | 236.40 kJ/mol |
| Fuel net calorific value | 50.000 MJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Actual flow at the chamber temperature | 37,824 m³/h |
| Residence time | 0.76143 s |
| Rate constant at T_c | 25.479 1/s |
| Destruction efficiency | 100.000 % |
| Gas temperature after heat recovery | 723.50 °C |
| Burner heat | 144.13 kW |
| Fuel | 10.377 kg/h |
Open this example in the calculator and change any input.
Formula
\(\tau = \frac{V}{Q_a}, \quad k = Ae^{-E/RT_c}, \quad DRE = 1 - e^{-k\tau}, \quad T_{pre} = T_{in} + \varepsilon(T_c - T_{in}), \quad Q_f = \dot mc_p(T_c - T_{pre})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_n\) | Gas flow at 0 °C, 1 atm | Nm³/s |
| \(T_{in}\) | Inlet gas temperature | K |
| \(T_c\) | Combustion chamber temperature | K |
| \(V\) | Chamber volume | m³ |
| \(\varepsilon\) | Heat recovery effectiveness (0 none, 0.6–0.7 recuperative, 0.95 regenerative) | - |
| \(c_p\) | Gas specific heat | J/(kg·K) |
| \(\log_{10}A\) | log₁₀ of the VOC rate constant A (1/s) | - |
| \(E\) | Activation energy | J/mol |
| \(LHV\) | Fuel net calorific value | J/kg |
| \(Q_a\) | Actual flow at the chamber temperature | m³/s |
| \(\tau\) | Residence time | s |
| \(k\) | Rate constant at T_c | 1/s |
| \(DRE\) | Destruction efficiency | - |
| \(T_{pre}\) | Gas temperature after heat recovery | K |
| \(Q_f\) | Burner heat | W |
| \(\dot m_f\) | Fuel | kg/s |
Method and standards
Plug-flow first-order oxidation and heat balance.
Where it is used
- Solvent, dryer and distillery vent oxidisers.
- RTO and recuperative oxidiser checks.
Common mistakes
- Relying on kinetics alone.
- Forgetting VOC heat at high concentrations (LEL limits).
Assumptions and limits
Fuel heat balance: Q_f = ṁ c_p (T_c − T_pre) with ṁ = 1.293 kg/Nm³ × Q_n, the whole net calorific value available, no burner or casing losses, no heat from the VOC itself and no extra flue gas from the fuel. At high VOC loading the VOC heat can cut the fuel substantially; losses raise it.
Plug flow; first-order kinetics.
References
- Cooper and Alley
- Air Pollution Control: A Design Approach
- 4th ed. (Waveland, 2011)
- ch. 13 (thermal oxidation: Arrhenius kinetics, residence time and fuel)
Questions and answers
Why does heat recovery matter so much?
Most of the fuel heats the air to oxidation temperature; a 95 % regenerative bed cuts fuel by about 20 times compared with none.
What is the three-T rule?
Time, temperature and turbulence: about 0.5–1 s, 760–870 °C and good mixing destroy most VOCs.
What do the defaults give?
10,000 Nm³/h at 760 °C in 8 m³: 0.76 s, essentially complete toluene destruction, about 144 kW burner heat with 95 % recovery.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.