FireCADCalc

Thermal Oxidiser: Residence Time, VOC Destruction and Fuel

Residence time, VOC destruction efficiency from Arrhenius kinetics and fuel needed by a thermal oxidiser, with recuperative or regenerative heat recovery.

Thermal power plantSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliserPulp and paper

Inputs

Examples: 10 000 Nm3/h toluene, 760 °C, RTO 95 %Recuperative 65 %, 700 °C

Results

Mixing, not kinetics, usually limits real oxidisers: design for 0.5–1 s at 760–870 °C (more for halogenated VOCs) and the permit's destruction efficiency. Burner heat is the sensible heat to raise the gas from T_pre to T_c with all the fuel's net heat available: burner and shell losses, VOC heat release (which lowers the fuel) and the added combustion products are neglected. Defaults: toluene kinetics as quoted by Cooper and Alley.

Actual flow at the chamber temperature37,824m³/h
Residence time0.76143s
Rate constant at T_c25.4791/s
Destruction efficiency100.000%
Gas temperature after heat recovery723.50°C
Burner heat144.13kW
Fuel10.377kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 000 Nm3/h toluene, 760 °C, RTO 95 %. The inputs, in the units selected above:

InputValue
Gas flow at 0 °C, 1 atm10,000 Nm³/h
Inlet gas temperature30.000 °C
Combustion chamber temperature760.00 °C
Chamber volume8.0000 m³
Heat recovery effectiveness (0 none, 0.6–0.7 recuperative, 0.95 regenerative)95.000 %
Gas specific heat1.1000 kJ/(kg·K)
log₁₀ of the VOC rate constant A (1/s)13.358 -
Activation energy236.40 kJ/mol
Fuel net calorific value50.000 MJ/kg

Applying the formula below gives:

ResultValue
Actual flow at the chamber temperature37,824 m³/h
Residence time0.76143 s
Rate constant at T_c25.479 1/s
Destruction efficiency100.000 %
Gas temperature after heat recovery723.50 °C
Burner heat144.13 kW
Fuel10.377 kg/h

Open this example in the calculator and change any input.

Formula

\(\tau = \frac{V}{Q_a}, \quad k = Ae^{-E/RT_c}, \quad DRE = 1 - e^{-k\tau}, \quad T_{pre} = T_{in} + \varepsilon(T_c - T_{in}), \quad Q_f = \dot mc_p(T_c - T_{pre})\)

Variables

Symbol Meaning SI unit
\(Q_n\) Gas flow at 0 °C, 1 atm Nm³/s
\(T_{in}\) Inlet gas temperature K
\(T_c\) Combustion chamber temperature K
\(V\) Chamber volume m³
\(\varepsilon\) Heat recovery effectiveness (0 none, 0.6–0.7 recuperative, 0.95 regenerative) -
\(c_p\) Gas specific heat J/(kg·K)
\(\log_{10}A\) log₁₀ of the VOC rate constant A (1/s) -
\(E\) Activation energy J/mol
\(LHV\) Fuel net calorific value J/kg
\(Q_a\) Actual flow at the chamber temperature m³/s
\(\tau\) Residence time s
\(k\) Rate constant at T_c 1/s
\(DRE\) Destruction efficiency -
\(T_{pre}\) Gas temperature after heat recovery K
\(Q_f\) Burner heat W
\(\dot m_f\) Fuel kg/s

Method and standards

Plug-flow first-order oxidation and heat balance.

Where it is used

  • Solvent, dryer and distillery vent oxidisers.
  • RTO and recuperative oxidiser checks.

Common mistakes

  • Relying on kinetics alone.
  • Forgetting VOC heat at high concentrations (LEL limits).

Assumptions and limits

  • Fuel heat balance: Q_f = ṁ c_p (T_c − T_pre) with ṁ = 1.293 kg/Nm³ × Q_n, the whole net calorific value available, no burner or casing losses, no heat from the VOC itself and no extra flue gas from the fuel. At high VOC loading the VOC heat can cut the fuel substantially; losses raise it.

  • Plug flow; first-order kinetics.

References

  • Cooper and Alley
  • Air Pollution Control: A Design Approach
  • 4th ed. (Waveland, 2011)
  • ch. 13 (thermal oxidation: Arrhenius kinetics, residence time and fuel)

Questions and answers

Why does heat recovery matter so much?

Most of the fuel heats the air to oxidation temperature; a 95 % regenerative bed cuts fuel by about 20 times compared with none.

What is the three-T rule?

Time, temperature and turbulence: about 0.5–1 s, 760–870 °C and good mixing destroy most VOCs.

What do the defaults give?

10,000 Nm³/h at 760 °C in 8 m³: 0.76 s, essentially complete toluene destruction, about 144 kW burner heat with 95 % recovery.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.