Transformer Short-Circuit Current (IEC 60909)

Three-phase fault current at the terminals of a transformer fed from an infinite source: the simple I/uk value and the IEC 60909 value with c, KT and peak current.

Thermal power plantProcess steam and utilities

Inputs

Examples: 1 000 kVA, 433 V, uk 5 %2 500 kVA, 6.6 kV, uk 8 %500 kVA, 415 V, uk 4.5 %

From the nameplate; IEC 60076-5 recognises minimum values of 4 % up to 630 kVA, 5 % to 1 250 kVA, 6 % to 2 500 kVA.
Maximum fault current: 1.05 for low voltage with +6 % tolerance, 1.10 for low voltage with +10 % and for voltages above 1 kV.
From the load losses: R = P_k / (3 I_r²). Typical 0.1–0.3 for distribution transformers, below 0.1 for large ones.

Results

Initial symmetrical short-circuit current (IEC 60909)3.0152kA
Peak short-circuit current7.6367kA
Short-circuit power34.469MVA
Simple estimate I_r / u_k2.7337kA
Rated current218.69A
Peak factor1.7909
Transformer correction factor0.99728
Transformer impedance referred to this side1,393.9mΩ

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 000 kVA, 433 V, uk 5 %. The inputs, in the units selected above:

InputValue
Rated power1,000.0 kVA
Rated voltage of the faulted side, line to line433.00 V
Short-circuit (impedance) voltage5.0000 %
Voltage factor c (IEC 60909-0 Table 1)1.0500 -
Resistance to reactance ratio of the transformer0.15000 -

Applying the formula below gives:

ResultValue
Initial symmetrical short-circuit current (IEC 60909)28.904 kA
Peak short-circuit current67.236 kA
Short-circuit power21.677 MVA
Simple estimate I_r / u_k26.667 kA
Rated current1,333.4 A
Peak factor1.6449
Transformer correction factor0.96876
Transformer impedance referred to this side9.3745 mΩ

Open this example in the calculator and change any input.

Formula

\(I_r = \frac{S_r}{\sqrt 3\,U_n} \qquad I_{k,0} = \frac{I_r}{u_k} \qquad Z_T = u_k\,\frac{U_n^2}{S_r}\)

IEC 60909-0, infinite source, with \(x_T = u_k/\sqrt{1 + (R/X)^2}\):

\(K_T = 0.95\,\frac{c_{max}}{1 + 0.6\,x_T} \qquad I_k'' = \frac{c_{max}\,U_n}{\sqrt 3\,K_T Z_T} \qquad S_k'' = \sqrt 3\,U_n I_k''\)

\(\kappa = 1.02 + 0.98\,e^{-3R/X} \qquad i_p = \kappa\sqrt 2\,I_k''\)

Variables

Symbol Meaning SI unit
\(S_r\) transformer rated power VA
\(U_n\) rated voltage of the faulted side, line to line V
\(u_k\) short-circuit (impedance) voltage –
\(c_{max}\) voltage factor of IEC 60909-0 –
\(R/X\) resistance to reactance ratio of the transformer –
\(I_k''\) initial symmetrical short-circuit current A
\(i_p\) peak short-circuit current A
\(S_k''\) short-circuit power VA
\(I_{k,0}\) simple estimate \(I_r/u_k\) A
\(I_r\) rated current A
\(\kappa\) peak factor –
\(K_T\) transformer impedance correction factor –
\(Z_T\) transformer impedance referred to the faulted side Ω
\(x_T\) relative reactance of the transformer –

Method and standards

IEC 60909-0:2016 for a three-phase short circuit fed by a network transformer from an infinite source: transformer impedance from its rated short-circuit voltage, the impedance correction factor K_T for network transformers, the voltage factor c_max of the standard's table, and the peak factor κ from R/X.

Where it is used

  • Rating switchgear and breakers.
  • Protection coordination studies.
  • Cable short-circuit withstand checks.

Common mistakes

  • Ignoring the source impedance (or assuming an infinite bus without saying so).
  • Using the wrong impedance base.
  • Forgetting motor contribution.

Assumptions and limits

  • One voltage U is used both as the system nominal voltage U_n (in c U_n) and as the transformer rated voltage U_rT (in Z_T). IEC 60909-0 keeps them apart: for a 433 V transformer on a 400 V system, the standard's result lies between the values obtained with U = 400 V and U = 433 V. Enter the value that matches your study basis.

  • Infinite source upstream; network, cable and motor contributions are not included (motors add to the fault current).

  • Three-phase symmetrical fault at the transformer terminals.

  • R/X from the transformer's load losses; R/X = 0 gives κ = 2, the upper bound.

References

  • IEC 60909-0:2016 (short-circuit currents in three-phase a.c. systems)
  • IEC 60076-5 (impedance values)

Questions and answers

What is the fault current of a 1 000 kVA transformer?

At 433 V with uk = 5 % the simple estimate is I_r/u_k = 1 333 A/0.05 = 26.7 kA. IEC 60909 with c = 1.05 and the transformer correction factor gives 28.9 kA, and a peak of 67.2 kA for R/X = 0.15.

Why is the IEC 60909 value higher?

The voltage factor c allows for the operating voltage being above nominal, and the correction factor K_T for the transformer's operating conditions. Both make the maximum fault current larger than the nameplate estimate.

Is the supply network included?

No, the source is taken as infinite, which gives the highest possible current at the transformer terminals. A real network impedance lowers it; this is the safe value for switchgear ratings.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.