Worked example
Example: 1 000 kVA, 433 V, uk 5 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated power | 1,000.0 kVA |
| Rated voltage of the faulted side, line to line | 433.00 V |
| Short-circuit (impedance) voltage | 5.0000 % |
| Voltage factor c (IEC 60909-0 Table 1) | 1.0500 - |
| Resistance to reactance ratio of the transformer | 0.15000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Initial symmetrical short-circuit current (IEC 60909) | 28.904 kA |
| Peak short-circuit current | 67.236 kA |
| Short-circuit power | 21.677 MVA |
| Simple estimate I_r / u_k | 26.667 kA |
| Rated current | 1,333.4 A |
| Peak factor | 1.6449 |
| Transformer correction factor | 0.96876 |
| Transformer impedance referred to this side | 9.3745 mΩ |
Open this example in the calculator and change any input.
Formula
\(I_r = \frac{S_r}{\sqrt 3\,U_n} \qquad I_{k,0} = \frac{I_r}{u_k} \qquad Z_T = u_k\,\frac{U_n^2}{S_r}\)
IEC 60909-0, infinite source, with \(x_T = u_k/\sqrt{1 + (R/X)^2}\):
\(K_T = 0.95\,\frac{c_{max}}{1 + 0.6\,x_T} \qquad I_k'' = \frac{c_{max}\,U_n}{\sqrt 3\,K_T Z_T} \qquad S_k'' = \sqrt 3\,U_n I_k''\)
\(\kappa = 1.02 + 0.98\,e^{-3R/X} \qquad i_p = \kappa\sqrt 2\,I_k''\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_r\) | transformer rated power | VA |
| \(U_n\) | rated voltage of the faulted side, line to line | V |
| \(u_k\) | short-circuit (impedance) voltage | – |
| \(c_{max}\) | voltage factor of IEC 60909-0 | – |
| \(R/X\) | resistance to reactance ratio of the transformer | – |
| \(I_k''\) | initial symmetrical short-circuit current | A |
| \(i_p\) | peak short-circuit current | A |
| \(S_k''\) | short-circuit power | VA |
| \(I_{k,0}\) | simple estimate \(I_r/u_k\) | A |
| \(I_r\) | rated current | A |
| \(\kappa\) | peak factor | – |
| \(K_T\) | transformer impedance correction factor | – |
| \(Z_T\) | transformer impedance referred to the faulted side | Ω |
| \(x_T\) | relative reactance of the transformer | – |
Method and standards
IEC 60909-0:2016 for a three-phase short circuit fed by a network transformer from an infinite source: transformer impedance from its rated short-circuit voltage, the impedance correction factor K_T for network transformers, the voltage factor c_max of the standard's table, and the peak factor κ from R/X.
Where it is used
- Rating switchgear and breakers.
- Protection coordination studies.
- Cable short-circuit withstand checks.
Common mistakes
- Ignoring the source impedance (or assuming an infinite bus without saying so).
- Using the wrong impedance base.
- Forgetting motor contribution.
Assumptions and limits
One voltage U is used both as the system nominal voltage U_n (in c U_n) and as the transformer rated voltage U_rT (in Z_T). IEC 60909-0 keeps them apart: for a 433 V transformer on a 400 V system, the standard's result lies between the values obtained with U = 400 V and U = 433 V. Enter the value that matches your study basis.
Infinite source upstream; network, cable and motor contributions are not included (motors add to the fault current).
Three-phase symmetrical fault at the transformer terminals.
R/X from the transformer's load losses; R/X = 0 gives κ = 2, the upper bound.
References
- IEC 60909-0:2016 (short-circuit currents in three-phase a.c. systems)
- IEC 60076-5 (impedance values)
Questions and answers
What is the fault current of a 1 000 kVA transformer?
At 433 V with uk = 5 % the simple estimate is I_r/u_k = 1 333 A/0.05 = 26.7 kA. IEC 60909 with c = 1.05 and the transformer correction factor gives 28.9 kA, and a peak of 67.2 kA for R/X = 0.15.
Why is the IEC 60909 value higher?
The voltage factor c allows for the operating voltage being above nominal, and the correction factor K_T for the transformer's operating conditions. Both make the maximum fault current larger than the nameplate estimate.
Is the supply network included?
No, the source is taken as infinite, which gives the highest possible current at the transformer terminals. A real network impedance lowers it; this is the safe value for switchgear ratings.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.