Motor Starting Current: DOL, Star-Delta and Autotransformer

Line starting current and starting torque of an induction motor started direct on line, star-delta or by autotransformer, from its locked-rotor current and torque.

Thermal power plantProcess steam and utilitiesElectric motor

Inputs

Examples: 110 A motor, 6.5 x FLC, 180 % LRT, DOL110 A motor, star-delta250 A motor, 6 x FLC, 150 % LRT, autotransformer 65 % tap

From the motor data sheet.
Used for the autotransformer starter only.

Results

DOL starting current I_DOL = k I_FL = 1500 A.

Check that the starting torque exceeds the load's breakaway torque with a margin; magnetising current and transition current peaks are not included.

Starting current drawn from the line633.75A
Starting current as a share of DOL current42.250%
Starting torque as a share of full-load torque63.375%
Voltage at the motor as a share of line voltage65.000%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 110 A motor, 6.5 x FLC, 180 % LRT, DOL. The inputs, in the units selected above:

InputValue
Full-load current110.00 A
Locked-rotor current as a multiple of full-load current6.5000 -
Locked-rotor torque as a share of full-load torque180.00 %
Starting methodDirect on line (DOL)
Autotransformer tap (share of line voltage)65.000 %

Applying the formula below gives:

ResultValue
Starting current drawn from the line715.00 A
Starting current as a share of DOL current100.00 %
Starting torque as a share of full-load torque180.00 %
Voltage at the motor as a share of line voltage100.00 %

Open this example in the calculator and change any input.

Formula

\(I_{DOL} = k I_{FL}\)

\(\text{star-delta: } I_{st} = I_{DOL}/3, \; T_{st} = T_{LR}/3\)

\(\text{autotransformer: } I_{st} = a^2 I_{DOL}, \; T_{st} = a^2 T_{LR}\)

Variables

Symbol Meaning SI unit
\(I_{FL}\) full-load current A
\(k\) locked-rotor current multiple -
\(T_{LR}\) locked-rotor torque as a share of full-load torque -
\(\text{method}\) starting method -
\(a\) autotransformer tap -
\(I_{DOL}\) direct-on-line starting current A
\(I_{st}\) line starting current A
\(I_{st} / I_{DOL}\) starting current as a share of DOL -
\(T_{st}\) starting torque as a share of full-load torque -
\(U_m / U\) voltage at the motor as a share of line voltage -

Method and standards

Locked-rotor current is proportional to the voltage across the windings and torque to its square. Star connection puts 1/√3 of line voltage on each winding; an autotransformer at tap a puts a times line voltage on the motor and, neglecting magnetising current, draws a² of the DOL current from the line.

Where it is used

  • Choosing a starter for a large pump or fan motor.
  • Checking whether the motor can still start its load.
  • Estimating starting current for voltage-dip and generator studies.

Common mistakes

  • Choosing star-delta for a load with high breakaway torque (it may not start).
  • Ignoring the current spike at the star-to-delta changeover.
  • Taking full-load current as the starting current.

Assumptions and limits

  • Steady locked-rotor values; transients and magnetising current not included. The DOL current I_DOL is given in a note.
  • An open-transition star-delta changeover can draw a peak above the DOL current; it is not included.
  • Soft starters and VFDs limit current by control, not by a fixed ratio.

References

  • Reduced-voltage starting relations (current and torque ∝ voltage², star 1/√3)

Questions and answers

What starting current does a 110 A motor draw DOL?

With 6.5 times full-load locked-rotor current, 715 A. Star-delta cuts it to a third, about 238 A, but also cuts starting torque to a third.

Why does star-delta cut current and torque to a third?

Each winding sees 1/√3 of line voltage in star; winding current and torque fall by 1/√3 and 1/3, and line current in star is a third of the delta DOL value.

What does an autotransformer at 65 % do?

The motor gets 65 % voltage, so its torque and the line current both fall to 0.65², about 42 % of DOL.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.