Motor Loading from Measured Input Power

Percentage loading of a three-phase motor from measured voltage, current and power factor against its rated output and efficiency, by the input power method.

Thermal power plantProcess steam and utilities

Inputs

Examples: 75 kW, 94 %: 410 V, 95 A, 0.8215 kW, 90 %: 415 V, 14 A, 0.6 (lightly loaded)200 kW, 95.5 %: 6.6 kV, 21 A, 0.88

Results

The rated efficiency is taken to hold at this load; below about 40 % load the real efficiency is lower and the loading is over-stated.

The motor is overloaded.

Measured input power √3 V I cos φ211.25kW
Input power at full load P_r / η_r209.42kW
Motor loading100.87%
Estimated shaft output201.75kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 75 kW, 94 %: 410 V, 95 A, 0.82. The inputs, in the units selected above:

InputValue
Rated output of the motor75.000 kW
Rated (full-load) efficiency94.000 %
Measured line voltage410.00 V
Measured line current95.000 A
Measured power factor0.82000 -

Applying the formula below gives:

ResultValue
Measured input power √3 V I cos φ55.320 kW
Input power at full load P_r / η_r79.787 kW
Motor loading69.334 %
Estimated shaft output52.001 kW

Open this example in the calculator and change any input.

Formula

\(P_{in} = \sqrt 3\, V I \cos\varphi, \quad L = \frac{P_{in}}{P_r / \eta_r}\)

Variables

Symbol Meaning SI unit
\(P_r\) Rated output of the motor W
\(\eta_r\) Rated (full-load) efficiency -
\(V\) Measured line voltage V
\(I\) Measured line current A
\(\cos\varphi\) Measured power factor -
\(P_{in}\) Measured input power √3 V I cos φ W
\(P_{in,r}\) Input power at full load P_r / η_r W
\(L\) Motor loading -
\(P_{out}\) Estimated shaft output W

Method and standards

Measured input against rated input.

Where it is used

  • Energy audits.
  • Finding oversized motors.

Common mistakes

  • Using nameplate power factor.
  • Clamp reading on one phase only.

Assumptions and limits

  • Balanced supply; efficiency constant with load.

References

  • Input power method (Bureau of Energy Efficiency, Guide Book 3, ch. 2; US DOE Motor Challenge fact sheet)

Questions and answers

How loaded is a 75 kW motor drawing 95 A at 410 V, 0.82 power factor?

Input 55.3 kW against 79.8 kW at full load: 69 %.

Why not use current alone?

Current falls less than load because the magnetising current stays; the power method is better.

What loading is good?

Motors are most efficient around 75 % load; much below 50 % wastes energy and power factor.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.