FireCADCalc

Energy-Efficient Motor Saving and Payback

Power, energy and cost saved by replacing a motor with a higher-efficiency one (IE2 to IE3 or IE4), and the simple payback on the extra cost.

Thermal power plantProcess steam and utilitiesIEC 60034 (rotating machines)Electric motor

Inputs

Examples: 55 kW at 75 %, 92 % to 95 %, 8000 h, 8/kWh15 kW at 80 %, 89 % to 92.5 %, 6000 h, 9/kWh200 kW at 70 %, 95 % to 96.5 %, 8400 h, 7/kWh

Results

Input power saved0.51017kW
Energy saved per year3,061.0kWh
Cost saved per year27,549
Simple payback (years)1.4519

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 55 kW at 75 %, 92 % to 95 %, 8000 h, 8/kWh. The inputs, in the units selected above:

InputValue
Motor rated output55.000 kW
Load factor (shaft load / rating)75.000 %
Efficiency of the existing motor at that load92.000 %
Efficiency of the new motor at that load95.000 %
Running hours per year8,000.0 h
Energy price per kWh (your currency)8.0000 -
Extra cost of the new motor (your currency)150,000 -

Applying the formula below gives:

ResultValue
Input power saved1.4159 kW
Energy saved per year11,327 kWh
Cost saved per year90,618
Simple payback (years)1.6553

Open this example in the calculator and change any input.

Formula

\(\Delta P = P_r\,L\left(\frac{1}{\eta_1} - \frac{1}{\eta_2}\right) \qquad \Delta E = \Delta P\,t \qquad S = \Delta E\,c_e \qquad n = \frac{C}{S}\)

Variables

Symbol Meaning SI unit
\(P_r\) rated output W
\(L\) load factor –
\(\eta_1\) existing efficiency –
\(\eta_2\) new efficiency –
\(t\) running hours per year s
\(c_e\) energy price per kWh currency
\(C\) extra cost currency
\(\Delta P\) input power saved W
\(\Delta E\) energy saved J
\(S\) cost saved per year currency
\(n\) simple payback years

Method and standards

Input power is shaft power divided by efficiency; the saving is the difference at the same shaft load.

Where it is used

  • Motor replacement policies.
  • Energy audits.
  • Choosing between rewinding and replacing.

Common mistakes

  • Using nameplate efficiency at part load.
  • Ignoring the higher speed of efficient motors.
  • Counting hours the motor is idle.

Assumptions and limits

  • Same shaft load before and after; no change in speed. Without a saving the payback is not shown.

References

  • IEC 60034-30-1 (efficiency classes)

Questions and answers

What does a 55 kW motor at 75 % load gain from 92 % to 95 % efficiency?

1.42 kW less input, 11 300 kWh a year at 8000 h; at 8 per kWh that is 90 600 a year, paying back 150 000 extra in 1.7 years.

Which efficiency do I enter?

Efficiency at the actual load, from the maker's data; rewound motors are often 1–2 points below nameplate.

Does a high-efficiency motor run faster?

Slightly (less slip), which can raise fan or pump power and eat part of the saving.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.