Worked example
Example: 470 µF at 400 V; 50 mH at 10 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Capacitance | 470.00 µF |
| Voltage on the capacitor (DC or instantaneous; peak for an AC capacitor) | 400.00 V |
| Inductance | 50.000 mH |
| Current in the inductor | 10.000 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy in the capacitor ½ C V² | 37.600 J |
| Charge C V | 0.18800 C |
| Energy in the inductor ½ L I² | 2.5000 J |
| Flux linkage L I | 0.50000 Wb |
Open this example in the calculator and change any input.
Formula
\(E_C = \tfrac12 C V^2, \quad Q = C V, \quad E_L = \tfrac12 L I^2, \quad \Psi = L I\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C\) | Capacitance | F |
| \(V\) | Voltage on the capacitor (DC or instantaneous; peak for an AC capacitor) | V |
| \(L\) | Inductance | H |
| \(I\) | Current in the inductor | A |
| \(E_C\) | Energy in the capacitor ½ C V² | J |
| \(Q\) | Charge C V | C |
| \(E_L\) | Energy in the inductor ½ L I² | J |
| \(\Psi\) | Flux linkage L I | Wb |
Method and standards
Stored field energy.
Where it is used
- Drive DC links and discharge resistors.
- Relay coil suppression.
Common mistakes
- µF entered as F.
- Using RMS for a DC bus.
Assumptions and limits
- Linear components.
- V and I are instantaneous (or DC) values. For an AC capacitor the peak stored energy uses the peak voltage √2 × V_rms; entering the RMS value gives half the peak energy (the same holds for the inductor current).
References
- E = ½ C V²
- E = ½ L I² (circuit theory)
Questions and answers
How much energy is in 470 µF at 400 V?
37.6 J, enough to be dangerous.
And in 50 mH carrying 10 A?
2.5 J.
Why discharge capacitors before work?
They hold their charge after switch-off; DC bus capacitors of drives can be lethal.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.