Worked example
Example: Illustrative 1.5 kN/m, 6 m, 15 deg, one sag rod. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gravity load on purlin per metre | 1.5000 kN/m |
| Roof slope | 15.000 ° |
| Purlin span (between rafters) | 6.0000 m |
| Sag rods | One at mid-span |
| Section modulus, strong axis | 89.000 cm³ |
| Section modulus, weak axis | 14.700 cm³ |
| Allowable bending stress | 165.00 MPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Strong-axis moment | 6.5200 kN·m |
| Weak-axis moment | 0.43676 kN·m |
| Strong-axis stress | 73.258 MPa |
| Weak-axis stress | 29.711 MPa |
| Combined stress ratio | 0.62406 |
Open this example in the calculator and change any input.
Formula
\(M_x = \frac{w\cos\theta L^2}{8}, \quad M_y = \frac{w\sin\theta (L/2)^2}{8}, \quad \eta = \frac{M_x/Z_x + M_y/Z_y}{f_b}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(w\) | Gravity load on purlin per metre | N/m |
| \(\theta\) | Roof slope | rad |
| \(L\) | Purlin span (between rafters) | m |
| \(n_{sag}\) | Sag rods | - |
| \(Z_x\) | Section modulus, strong axis | m³ |
| \(Z_y\) | Section modulus, weak axis | m³ |
| \(f_b\) | Allowable bending stress | Pa |
| \(M_x\) | Strong-axis moment | N·m |
| \(M_y\) | Weak-axis moment | N·m |
| \(f_{bx}\) | Strong-axis stress | Pa |
| \(f_{by}\) | Weak-axis stress | Pa |
| \(\eta\) | Combined stress ratio | - |
Method and standards
Purlin bending.
Where it is used
- Industrial shed and boiler house roofs.
- Side rails (girts) with the same method.
Common mistakes
- Ignoring the weak-axis component.
- Using sag rods without anchoring them at the ridge.
Assumptions and limits
- Load through the shear centre; simple strong-axis span.
References
- Biaxial bending with continuous weak-axis spans
Questions and answers
Why use sag rods?
Purlins are weak about the axis along the roof; sag rods cut that span, reducing weak-axis bending and twisting.
Which load cases matter?
Dead plus live or snow downward, and dead minus wind suction upward, which puts the unbraced bottom flange in compression.
What do the defaults represent?
An illustrative 1.5 kN/m on a channel purlin (Z_x 89 cm³, Z_y 14.7 cm³) spanning 6 m on a 15° roof with one mid-span sag rod and 165 MPa allowable.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Subramanian, Design of Steel Structures (Oxford University Press, 2008)