Worked example
Example: Illustrative 350 mm beam with 1.5 m slab. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steel beam area | 5,380.0 mm² |
| Steel beam depth | 350.00 mm |
| Top flange width | 140.00 mm |
| Top flange thickness | 12.200 mm |
| Steel design strength | 250.00 MPa |
| Effective slab width | 1.5000 m |
| Slab thickness | 120.00 mm |
| Concrete stress-block strength | 17.000 MPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Slab compressive force | 1,345.0 kN |
| PNA depth below slab top | 52.745 mm |
| PNA location (0 slab, 1 top flange) | 0 |
| Plastic moment | 361.30 kN·m |
Open this example in the calculator and change any input.
Formula
\(x = \frac{A_sf_y}{f_{cd}b_{eff}}, \quad M_p = A_sf_y\left(t_s + \frac{h}{2} - \frac{x}{2}\right)\ (x \le t_s)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_s\) | Steel beam area | m² |
| \(h\) | Steel beam depth | m |
| \(b_f\) | Top flange width | m |
| \(t_f\) | Top flange thickness | m |
| \(f_y\) | Steel design strength | Pa |
| \(b_{eff}\) | Effective slab width | m |
| \(t_s\) | Slab thickness | m |
| \(f_{cd}\) | Concrete stress-block strength | Pa |
| \(C_c\) | Slab compressive force | N |
| \(y_{pna}\) | PNA depth below slab top | m |
| \(\text{case}\) | PNA location (0 slab, 1 top flange) | - |
| \(M_p\) | Plastic moment | N·m |
Method and standards
Composite section.
Where it is used
- Floor beams in plant buildings and platforms.
- Bridge stringers with concrete decks.
Common mistakes
- Using gross slab width beyond the effective width.
- Assuming full interaction with too few studs.
Assumptions and limits
- Doubly symmetric steel section; full shear connection; concrete tension ignored.
References
- Rigid-plastic analysis of composite sections
Questions and answers
Why is a composite beam so much stronger?
The slab carries the compression far above the steel, giving a long lever arm for the steel's tension.
What is full shear connection?
Enough shear studs to transfer the full compressive force between slab and steel, so the section reaches its plastic moment.
What do the defaults represent?
An illustrative 350 mm I-beam (5,380 mm², 140 × 12.2 mm flange) at 250 MPa under a 1.5 m × 120 mm slab with 17 MPa stress-block strength.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Johnson, Composite Structures of Steel and Concrete, 3rd ed. (Blackwell, 2004)