Rectangular Combined Footing for Two Columns

Length and width of a rectangular combined footing giving uniform soil pressure under two column loads, with the maximum shear and hogging moment between columns.

Thermal power plantProcess steam and utilitiesSugar mill and cogeneration

Inputs

Examples: Illustrative 900 and 1300 kN at 5 mEqual loads 1000 kN at 4 mHeavy interior column

Accepted: 1 to 100,000 kN
Accepted: 1 to 100,000 kN
Accepted: 0.5 to 30 m
Accepted: 0.05 to 5 m
Accepted: 10 to 2,000 kPa

Results

The footing centroid is placed under the load resultant: L = 2(a + x̄), x̄ = P₂s/(P₁ + P₂), B = ΣP/(q_aL). As a beam loaded upward by w = ΣP/L, the largest hogging moment is where shear is zero, x₀ = P₁/w from the edge. Apply load factors and the user's concrete code for depth and steel; the interior column also needs a punching check.

Resultant from exterior column4.6154m
Footing length9.6308m
Footing width1.0799m
Maximum shear at a column centreline1,073.8kN
Maximum hogging moment between columns546.75kN·m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 900 and 1300 kN at 5 m. The inputs, in the units selected above:

InputValue
Exterior column load (service)900.00 kN
Interior column load (service)1,300.0 kN
Column spacing5.0000 m
Footing edge to exterior column centre0.25000 m
Net allowable soil pressure200.00 kPa

Applying the formula below gives:

ResultValue
Resultant from exterior column2.9545 m
Footing length6.4091 m
Footing width1.7163 m
Maximum shear at a column centreline902.13 kN
Maximum hogging moment between columns954.86 kN·m

Open this example in the calculator and change any input.

Formula

\(\bar x = \frac{P_2s}{P_1 + P_2}, \quad L = 2(a + \bar x), \quad B = \frac{P_1 + P_2}{q_aL}, \quad M_{max} = P_1(x_0 - a) - \frac{wx_0^2}{2}\)

Variables

Symbol Meaning SI unit
\(P_1\) Exterior column load (service) N
\(P_2\) Interior column load (service) N
\(s\) Column spacing m
\(a\) Footing edge to exterior column centre m
\(q_{a}\) Net allowable soil pressure Pa
\(\bar x\) Resultant from exterior column m
\(L\) Footing length m
\(B\) Footing width m
\(V_{max}\) Maximum shear at a column centreline N
\(M_{max}\) Maximum hogging moment between columns N·m

Method and standards

Combined footing.

Where it is used

  • Boundary columns in buildings and plant structures.
  • Closely spaced equipment supports.

Common mistakes

  • Making the footing symmetric about the columns rather than the resultant.
  • Forgetting to factor loads for design.

Assumptions and limits

  • Rigid footing; uniform pressure; vertical loads only.

References

  • Rigid combined footing with uniform pressure

Questions and answers

When is a combined footing needed?

When an exterior column sits at a property line, or two columns are so close that their footings would overlap.

What if the exterior load is larger?

The resultant moves outward; a rectangular footing may not fit, and a trapezoidal or strap footing is used.

What do the defaults represent?

Illustrative columns of 900 and 1,300 kN at 5 m spacing, the exterior one 0.25 m from the property line, on 200 kPa net allowable pressure.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bowles, Foundation Analysis and Design, 5th ed. (McGraw-Hill, 1996), Das, Principles of Foundation Engineering, 7th ed. (Cengage, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.