Worked example
Example: Illustrative 250 t block at 600 rpm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Block length | 6.0000 m |
| Block width | 4.0000 m |
| Mass of block and machine | 250.00 t |
| Soil shear modulus | 60.000 MPa |
| Soil Poisson's ratio | 0.33000 - |
| Soil density | 1,800.0 kg/m³ |
| Unbalanced force amplitude | 20.000 kN |
| Operating speed | 600.00 rpm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Equivalent radius | 2.7640 m |
| Vertical stiffness | 990,073 kN/m |
| Undamped natural frequency | 10.016 Hz |
| Geometric damping ratio | 0.40490 |
| Frequency ratio | 0.99843 |
| Vertical amplitude | 24.984 µm |
Open this example in the calculator and change any input.
Formula
\(k_z = \frac{4Gr_0}{1 - \nu}, \quad B_z = \frac{(1 - \nu)m}{4\rho r_0^3}, \quad D_z = \frac{0.425}{\sqrt{B_z}}, \quad A_z = \frac{F_0/k_z}{\sqrt{(1 - r^2)^2 + (2D_zr)^2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | Block length | m |
| \(B\) | Block width | m |
| \(m\) | Mass of block and machine | kg |
| \(G\) | Soil shear modulus | Pa |
| \(\nu\) | Soil Poisson's ratio | - |
| \(\rho_s\) | Soil density | kg/m³ |
| \(F_0\) | Unbalanced force amplitude | N |
| \(n\) | Operating speed | rad/s |
| \(r_0\) | Equivalent radius | m |
| \(k_z\) | Vertical stiffness | N/m |
| \(f_n\) | Undamped natural frequency | 1/s |
| \(D_z\) | Geometric damping ratio | - |
| \(r\) | Frequency ratio | - |
| \(A_z\) | Vertical amplitude | m |
Method and standards
Block foundation.
Where it is used
- Compressor, pump and fan foundations.
- Turbine-generator and crusher pedestals.
Common mistakes
- Using static soil modulus.
- Ignoring embedment, which stiffens and damps the block.
Assumptions and limits
- Rigid block on surface of elastic half-space; vertical mode only; constant force amplitude.
References
- Lysmer's analog for vertical vibration
Questions and answers
Why is soil damping so high for vertical vibration?
Waves radiate energy into the half-space; vertical modes of heavy-footed blocks often have 20–50 % damping.
Where does G come from?
From shear wave velocity, G = ρV_s², measured by seismic tests at the site.
What do the defaults represent?
An illustrative 6 m × 4 m block of 250 t on soil with G 60 MPa, ν 0.33 and 1,800 kg/m³, with a 20 kN unbalanced force at 600 rpm.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Richart, Hall and Woods, Vibrations of Soils and Foundations (Prentice Hall, 1970)