Worked example
Example: Illustrative 900 and 1300 kN at 5 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Exterior column load (service) | 900.00 kN |
| Interior column load (service) | 1,300.0 kN |
| Column spacing | 5.0000 m |
| Footing edge to exterior column centre | 0.25000 m |
| Net allowable soil pressure | 200.00 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resultant from exterior column | 2.9545 m |
| Footing length | 6.4091 m |
| Footing width | 1.7163 m |
| Maximum shear at a column centreline | 902.13 kN |
| Maximum hogging moment between columns | 954.86 kN·m |
Open this example in the calculator and change any input.
Formula
\(\bar x = \frac{P_2s}{P_1 + P_2}, \quad L = 2(a + \bar x), \quad B = \frac{P_1 + P_2}{q_aL}, \quad M_{max} = P_1(x_0 - a) - \frac{wx_0^2}{2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_1\) | Exterior column load (service) | N |
| \(P_2\) | Interior column load (service) | N |
| \(s\) | Column spacing | m |
| \(a\) | Footing edge to exterior column centre | m |
| \(q_{a}\) | Net allowable soil pressure | Pa |
| \(\bar x\) | Resultant from exterior column | m |
| \(L\) | Footing length | m |
| \(B\) | Footing width | m |
| \(V_{max}\) | Maximum shear at a column centreline | N |
| \(M_{max}\) | Maximum hogging moment between columns | N·m |
Method and standards
Combined footing.
Where it is used
- Boundary columns in buildings and plant structures.
- Closely spaced equipment supports.
Common mistakes
- Making the footing symmetric about the columns rather than the resultant.
- Forgetting to factor loads for design.
Assumptions and limits
- Rigid footing; uniform pressure; vertical loads only.
References
- Rigid combined footing with uniform pressure
Questions and answers
When is a combined footing needed?
When an exterior column sits at a property line, or two columns are so close that their footings would overlap.
What if the exterior load is larger?
The resultant moves outward; a rectangular footing may not fit, and a trapezoidal or strap footing is used.
What do the defaults represent?
Illustrative columns of 900 and 1,300 kN at 5 m spacing, the exterior one 0.25 m from the property line, on 200 kPa net allowable pressure.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Bowles, Foundation Analysis and Design, 5th ed. (McGraw-Hill, 1996), Das, Principles of Foundation Engineering, 7th ed. (Cengage, 2011)