Bulk Milk Cooling Load and Time

Refrigeration to cool milk in a bulk tank or plate cooler from collection to storage temperature within a set time, with the pre-cooling by well water.

Food, dairy and textile

Inputs

Examples: 5 t from 35 °C, pre-cooled to 20, to 4 °C in 3 hNo pre-cooling

Results

This is the average product load only: add tank and agitator heat gains and a margin to size the compressor.

Heat removed by pre-cooling0kWh
Heat removed by refrigeration67.683kWh
Refrigeration capacity for the milk alone (average)33.842kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 t from 35 °C, pre-cooled to 20, to 4 °C in 3 h. The inputs, in the units selected above:

InputValue
Milk5,000.0 kg
Milk specific heat3.9300 kJ/(kg·K)
Milk in35.000 °C
Milk after pre-cooling20.000 °C
Storage temperature4.0000 °C
Cooling time3.0000 h

Applying the formula below gives:

ResultValue
Heat removed by pre-cooling81.875 kWh
Heat removed by refrigeration87.333 kWh
Refrigeration capacity for the milk alone (average)29.111 kW

Open this example in the calculator and change any input.

Formula

\(Q_{pc} = Mc_p(T_1 - T_{pc}), \quad Q_r = Mc_p(T_{pc} - T_2), \quad \dot Q_r = \frac{Q_r}{t}\)

Variables

Symbol Meaning SI unit
\(M\) Milk kg
\(c_p\) Milk specific heat J/(kg·K)
\(T_1\) Milk in K
\(T_{pc}\) Milk after pre-cooling K
\(T_2\) Storage temperature K
\(t\) Cooling time s
\(Q_{pc}\) Heat removed by pre-cooling J
\(Q_r\) Heat removed by refrigeration J
\(\dot Q_r\) Refrigeration capacity W

Method and standards

Sensible heat balance.

Where it is used

  • Chilling centres and farm tanks.

Common mistakes

  • Ignoring pre-cooling.
  • Using kW for kWh.

Assumptions and limits

  • Uniform cooling of one batch. The capacity is the average product load: tank and agitator gains and a margin are extra. Bulk tanks filled over several milkings, where warm milk is added to cold (blend temperature limits), are not modelled.

References

  • Mass and energy balances (definitions)

Questions and answers

How fast must milk be cooled?

Usually to 4 °C within 2–3 hours of milking; check local rules.

Why pre-cool with water?

Well water takes milk from 35 °C to about 20 °C at almost no cost, halving the refrigeration.

Is the compressor capacity the same as the load?

Add tank and agitator gains and a margin.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.