Ice Bank (Ice Builder) Sizing

Ice to build for a peak cooling demand above the chiller's direct capacity, the ice-building refrigeration over the charging hours, and the ice volume.

Food, dairy and textile

Inputs

Examples: 500 kW peak for 4 h, 150 kW directSmall dairy 200 kW for 2 h

Results

Ice-building compressors run at low suction temperature, so their capacity is below the chiller's rating.

Cooling to store as ice330.00kWh
Ice to build3.5617t
Ice volume3.8853m³
Ice-building refrigeration27.500kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 kW peak for 4 h, 150 kW direct. The inputs, in the units selected above:

InputValue
Peak cooling load500.00 kW
Duration of the peak4.0000 h
Load met directly by the chiller during the peak150.00 kW
Ice-building hours16.000 h
Margin on ice15.000 %

Applying the formula below gives:

ResultValue
Cooling to store as ice1,610.0 kWh
Ice to build17.377 t
Ice volume18.956 m³
Ice-building refrigeration100.62 kW

Open this example in the calculator and change any input.

Formula

\(E = \max(Q_p - Q_d, 0)\,t_p(1 + f_s), \quad M_i = \frac{E}{\lambda_f}, \quad \dot Q_c = \frac{E}{t_c}\)

Variables

Symbol Meaning SI unit
\(Q_p\) Peak cooling load W
\(t_p\) Duration of the peak s
\(Q_d\) Load met directly by the chiller during the peak W
\(t_c\) Ice-building hours s
\(f_s\) Margin on ice -
\(E\) Cooling to store as ice J
\(M_i\) Ice to build kg
\(V_i\) Ice volume m³
\(\dot Q_c\) Ice-building refrigeration W

Method and standards

Latent heat storage balance.

Where it is used

  • Dairy and beverage refrigeration.

Common mistakes

  • Ignoring direct chiller capacity during the peak.

Assumptions and limits

  • All stored ice melts in the peak. Only latent heat is counted: the sensible cooling of the returning water to 0 °C and the tank's heat gains while building are left to the margin f_s.
  • When the chiller covers the peak the ice is zero and a note says so.

References

  • Mass and energy balances (definitions); latent heat of fusion 333.55 kJ/kg and ice density 916.7 kg/m³ at 0 °C

Questions and answers

Why an ice bank?

Dairies have short, sharp cooling peaks; ice built overnight meets them with a smaller compressor.

How much ice per kWh?

About 10.8 kg of ice stores 1 kWh of cooling.

What margin?

10–20 % for melting losses and uneven build.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.