Worked example
Example: Coal 12 t/h, 24 h/day, 30 days, 0.8 t/m³. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Average fuel firing rate | 12,000 kg/h |
| Running hours per day | 24.000 h |
| Days of stock | 30.000 - |
| Bulk density (liquid density for oil) | 800.00 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fuel to stock | 8,640.0 t |
| Volume of the stock | 10,800 m³ |
| Fuel burnt per day | 288.00 t |
Open this example in the calculator and change any input.
Formula
\(m_d = \dot m_f\,t_d \qquad m = m_d\,d \qquad V = \frac{m}{\rho_b}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_f\) | average fuel firing rate | kg/s |
| \(t_d\) | running hours per day | s |
| \(d\) | days of stock | – |
| \(\rho_b\) | bulk density (liquid density for oil) | kg/m³ |
| \(m\) | fuel to stock | kg |
| \(V\) | volume of the stock | m³ |
| \(m_d\) | fuel burnt per day | kg |
Method and standards
Mass and volume balance at the average firing rate.
Where it is used
- Planning coal yards, biomass sheds and oil tanks.
- Setting minimum stock levels.
- Checking storage after a load increase.
Common mistakes
- Using design firing rate when actual load is lower.
- Ignoring moisture changes in stored fuel.
- Counting unusable stock below the reclaim level.
Assumptions and limits
- Average firing rate over the stock period; use the MCR rate for a conservative stock.
- Stockpile losses, moisture changes and unusable heel in tanks are not included.
References
- Mass and volume balance
Questions and answers
How much coal should be stocked?
Firing rate × hours per day × days. A boiler burning 12 t/h around the clock needs 288 t a day, 8 640 t for 30 days, about 10 800 m³ at 0.8 t/m³.
How many days?
As your specification, fuel contract or regulator requires; the calculator does not suggest a number.
Does it size the stockpile area?
It gives the volume. The area follows from the pile shape and height the yard allows.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.