Worked example
Example: 2 t/h, factor 2.5, 40 cSt, 1½-in.. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total burner consumption | 2,000.0 kg/h |
| Circulation factor (flow / consumption) | 2.5000 - |
| Oil density at line temperature | 920.00 kg/m³ |
| Kinematic viscosity at line temperature | 40.000 cSt |
| Pipe inside diameter | 40.900 mm |
| Equivalent ring length | 300.00 m |
| Pressure to hold at the burners | 25.000 bar |
| Pump efficiency | 50.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Circulating flow | 5.4348 m³/h |
| Velocity | 1.1491 m/s |
| Reynolds number | 1,174.9 |
| Ring friction drop | 2.4267 bar |
| Pump differential | 27.427 bar |
| Pump power | 8.2810 kW |
Open this example in the calculator and change any input.
Formula
\(Q = \frac{k\dot m_b}{\rho}, \quad Re = \frac{Vd}{\nu}, \quad \Delta p_f = f_D\frac{L_e}{d}\frac{\rho V^2}{2}, \quad P = \frac{Q\Delta p}{\eta}\)
\(V = \frac{4Q}{\pi d^2}, \quad f_D = \frac{64}{Re}\ (Re < 2300), \quad \frac{1}{\sqrt{f_D}} = -2\log_{10}\left(\frac{\varepsilon/d}{3.7} + \frac{2.51}{Re\sqrt{f_D}}\right)\ \text{otherwise}, \quad \Delta p = \Delta p_f + \Delta p_b\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_b\) | Total burner consumption | kg/s |
| \(k\) | Circulation factor (flow / consumption) | - |
| \(\rho\) | Oil density at line temperature | kg/m³ |
| \(\nu\) | Kinematic viscosity at line temperature | m²/s |
| \(d\) | Pipe inside diameter | m |
| \(L_e\) | Equivalent ring length | m |
| \(\Delta p_b\) | Pressure to hold at the burners | Pa |
| \(\eta\) | Pump efficiency | - |
| \(Q\) | Circulating flow | m³/s |
| \(V\) | Velocity | m/s |
| \(Re\) | Reynolds number | - |
| \(\Delta p_f\) | Ring friction drop | Pa |
| \(\Delta p\) | Pump differential | Pa |
| \(P\) | Pump power | W |
| \(f_D\) | Darcy friction factor | - |
| \(\varepsilon\) | pipe roughness, 0.045 mm (commercial steel) | m |
Method and standards
Darcy–Weisbach pipe friction with the laminar factor 64/Re below Re 2300 and Colebrook above, for commercial steel pipe (roughness 0.045 mm).
Where it is used
- Burner fuel systems for boilers and furnaces.
- Checking ring pressure after adding burners.
Common mistakes
- Using cold-oil viscosity at line temperature or the reverse.
- Undersizing the return to tank.
Assumptions and limits
- Isothermal line.
- The full circulating flow is taken along the whole equivalent length; burner off-takes along the ring, static head and filter and heater drops are not included.
- In the transition range (Re 2300–4000) a note appears.
References
- Darcy–Weisbach with laminar and Colebrook friction (FireCAD engine) and circulation balance (definitions)
Questions and answers
Why circulate more than the burners use?
Excess flow keeps the ring hot and the pressure steady as burners start and stop; 2–3 times consumption is usual.
Why is heavy oil flow laminar?
Even heated, heavy oil is viscous; Reynolds numbers of a few hundred are common, so friction is 64/Re.
What do the defaults give?
2 t/h burners, factor 2.5 at 40 cSt in 1½-in. pipe: about 5.4 m³/h, 1.15 m/s, laminar (Re about 1,200), about 2.4 bar of friction.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.