FireCADCalc

Fuel Oil Ring Main: Circulation Flow, Pipe Size and Pressure Drop

Circulating flow, velocity, Reynolds number, pressure drop and pump power of a fuel oil ring main from burner use, circulation factor and oil properties.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserFood, dairy and textile

Inputs

Examples: 2 t/h, factor 2.5, 40 cSt, 1½-in.Light oil 600 kg/h, 5 cSt, 1-in.

Results

Circulating flow5.4348m³/h
Velocity1.1491m/s
Reynolds number1,174.9
Ring friction drop2.4267bar
Pump differential27.427bar
Pump power8.2810kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 t/h, factor 2.5, 40 cSt, 1½-in.. The inputs, in the units selected above:

InputValue
Total burner consumption2,000.0 kg/h
Circulation factor (flow / consumption)2.5000 -
Oil density at line temperature920.00 kg/m³
Kinematic viscosity at line temperature40.000 cSt
Pipe inside diameter40.900 mm
Equivalent ring length300.00 m
Pressure to hold at the burners25.000 bar
Pump efficiency50.000 %

Applying the formula below gives:

ResultValue
Circulating flow5.4348 m³/h
Velocity1.1491 m/s
Reynolds number1,174.9
Ring friction drop2.4267 bar
Pump differential27.427 bar
Pump power8.2810 kW

Open this example in the calculator and change any input.

Formula

\(Q = \frac{k\dot m_b}{\rho}, \quad Re = \frac{Vd}{\nu}, \quad \Delta p_f = f_D\frac{L_e}{d}\frac{\rho V^2}{2}, \quad P = \frac{Q\Delta p}{\eta}\)

\(V = \frac{4Q}{\pi d^2}, \quad f_D = \frac{64}{Re}\ (Re < 2300), \quad \frac{1}{\sqrt{f_D}} = -2\log_{10}\left(\frac{\varepsilon/d}{3.7} + \frac{2.51}{Re\sqrt{f_D}}\right)\ \text{otherwise}, \quad \Delta p = \Delta p_f + \Delta p_b\)

Variables

Symbol Meaning SI unit
\(\dot m_b\) Total burner consumption kg/s
\(k\) Circulation factor (flow / consumption) -
\(\rho\) Oil density at line temperature kg/m³
\(\nu\) Kinematic viscosity at line temperature m²/s
\(d\) Pipe inside diameter m
\(L_e\) Equivalent ring length m
\(\Delta p_b\) Pressure to hold at the burners Pa
\(\eta\) Pump efficiency -
\(Q\) Circulating flow m³/s
\(V\) Velocity m/s
\(Re\) Reynolds number -
\(\Delta p_f\) Ring friction drop Pa
\(\Delta p\) Pump differential Pa
\(P\) Pump power W
\(f_D\) Darcy friction factor -
\(\varepsilon\) pipe roughness, 0.045 mm (commercial steel) m

Method and standards

Darcy–Weisbach pipe friction with the laminar factor 64/Re below Re 2300 and Colebrook above, for commercial steel pipe (roughness 0.045 mm).

Where it is used

  • Burner fuel systems for boilers and furnaces.
  • Checking ring pressure after adding burners.

Common mistakes

  • Using cold-oil viscosity at line temperature or the reverse.
  • Undersizing the return to tank.

Assumptions and limits

  • Isothermal line.
  • The full circulating flow is taken along the whole equivalent length; burner off-takes along the ring, static head and filter and heater drops are not included.
  • In the transition range (Re 2300–4000) a note appears.

References

  • Darcy–Weisbach with laminar and Colebrook friction (FireCAD engine) and circulation balance (definitions)

Questions and answers

Why circulate more than the burners use?

Excess flow keeps the ring hot and the pressure steady as burners start and stop; 2–3 times consumption is usual.

Why is heavy oil flow laminar?

Even heated, heavy oil is viscous; Reynolds numbers of a few hundred are common, so friction is 64/Re.

What do the defaults give?

2 t/h burners, factor 2.5 at 40 cSt in 1½-in. pipe: about 5.4 m³/h, 1.15 m/s, laminar (Re about 1,200), about 2.4 bar of friction.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.